Representative image shown

MO132-0.16

Manual Motor Starter Magnetic Only (0.16 A)

$156.88
Factory New

ABB, Manual Motor Starter, Compact 45 mm wide magnetic-only, 0.16 A rated operational current, Designed to safely switch and provide fuse-less short-circuit protection for single- and three-phase applications

Representative image shown
Product Details
SKU:
MO132-0.16
UPC:
4013614400162
Weight:
0.47 LBS
Width:
1.77 in
Height:
3.54 in
Depth:
3.41 in
Rated Operational Voltage:
690 V AC
Number of Poles:
3 Poles
Terminal Type:
Screw Terminals
Current Range:
0.10 A to 0.16 A

Complete Your Build
verified Verified fit These products are compatible with the

Auxiliary Contacts
Signaling Contacts
Shunt Trips
Undervoltage Releases
Busbars
Terminal Blocks
Enclosures
Shafts
Enclosures
Shafts

Build My Enclosure

Total price: $0

Description

Description

The MO132-0.16 manual motor starter magnetic only is a compact 45 mm width device with a rated operational current of Ie = 0.16 A. This device is used to manually switch on and off loads/motors and to protect them reliably and without the need for a fuse from short-circuits. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 100 kA at 400 V AC. A combination together with overload relays or motor controllers allows the protection of motors. Further features are the built-in disconnect function, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter magnetic only is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks are available as accessory.

Specifications

Specifications

Technical

 
Rated Service Short-Circuit Breaking Capacity (Ics):
(230 V AC) 100 kA
(400 V AC) 100 kA
(440 V AC) 100 kA
(500 V AC) 100 kA
(690 V AC) 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(230 V AC) 100 kA
(400 V AC) 100 kA
(440 V AC) 100 kA
(500 V AC) 100 kA
(690 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (Ii): 2 A
Setting Range: None
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 0.03 kW
Rated Operational Power AC-3e (Pe): (400 V) Three Phase 0.03 kW
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 0.16 A
Rated Operational Current AC-3 (Ie): 0.16 A
Rated Operational Current AC-3e (Ie): 0.16 A
Rated Frequency (f):
Main Circuit 50 Hz
Main Circuit 60 Hz
Operating Frequency (fsw): 0 ... 400 Hz
Rated Impulse Withstand Voltage (Uimp): Main Circuit 6 kV
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 1.7 W
Number of Poles: 3P
Conventional Free-air Thermal Current (Ith): Main Circuit 0.16 A
Degree of Protection:
Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 50000 cycle
Mechanical Durability: Nr. Operations 100000 cycle
Terminal Type: Screw Terminals
Connecting Capacity Main Circuit:
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque: Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Main Circuit 9 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: 1 ... 6
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance:
Electrical Conductive Board, Horizontal - Up to 400 V 0 mm
Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
Contact Position Indication: ON / OFF / TRIP
Standards:
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
IEC 60335-2-40 A2L
Remarks: For overload protection of the motors, an appropriate thermal or electronic overload relays must be used

Technical UL/CSA

 
Short-Circuit Current Rating (SCCR):
Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 47 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 47 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA
Maximum Operating Voltage UL/CSA: Main Circuit 600 V AC
Full Load Amps Motor Use:
(200 V AC) Three Phase 0.16 A
(208 V AC) Three Phase 0.16 A
(220 ... 240 V AC) Three Phase 0.16 A
(440 ... 480 V AC) Three Phase 0.16 A
(550 ... 600 V AC) Three Phase 0.16 A
Locked Rotor Amps:
(200 V AC) Three Phase 0.96 A
(208 V AC) Three Phase 0.96 A
(220 ... 240 V AC) Three Phase 0.96 A
(440 ... 480 V AC) Three Phase 0.96 A
(550 ... 600 V AC) Three Phase 0.96 A
General Use Rating UL/CSA: (600 V AC) 0.16 A
Connecting Capacity Main Circuit UL/CSA:
Flexible 1/2x 16-12 AWG
Stranded 1/2x 16-12 AWG
Tightening Torque UL/CSA: Main Circuit 10 in·lb

Environmental

 
Ambient Air Temperature:
Around the Enclosure 0 ... +40 °C
Operation -25 ... +60 °C
Storage -50 ... +80 °C
Ambient Air Temperature Compensation: No
Maximum Operating Altitude Permissible: 2000 m
Resistance to Shock acc. to IEC 60068-2-27: 11 ms Pulse 25g
Resistance to Vibrations: 5g 3 ... 150 Hz