Description
Description
S1-M2-25 three phase feeder terminals allow the connection of bigger cable cross sections up to 25mm². They are usable with MS116 and MS132 manual motor starters and have a high mounting form. The rated current is 65 A.
Specifications
Specifications
Technical |
|
| Rated Operational Voltage: |
690 V AC
250 V DC
|
| Rated Operational Current (Ie): | 65 A |
| Number of Poles: | 3P |
| Degree of Protection: | IP20 |
| Terminal Type: | Screw Terminals |
| Connecting Capacity Main Circuit: |
Flexible with Ferrule 1x 2.5 ... 16 mm²
Flexible with Insulated Ferrule 1x 2.5 ... 16 mm²
Flexible 1x 2.5 ... 16 mm²
Rigid 1x 2.5 ... 25 mm²
|
| Tightening Torque: | Main Circuit 2.5 N·m |
| Wire Stripping Length: | Main Circuit 10 mm |
| Recommended Screw Driver: |
M3.5
Pozidriv 2
|
| Standards: |
IEC/EN 60947-1
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
|
| Remarks: |
High
|
Technical UL/CSA |
|
| Maximum Operating Voltage UL/CSA: | Main Circuit 600 V AC |
| Connecting Capacity Main Circuit UL/CSA: |
Flexible 1x 12-6 AWG
Stranded 1x 12-4 AWG
|
| Tightening Torque UL/CSA: | Main Circuit 22 in·lb |
Environmental |
|
| Ambient Air Temperature: |
Operation -25 ... +70 °C
Storage -50 ... +80 °C
|