Representative image shown

MO132-20

Manual Motor Starter Magnetic Only (20 A)

$181.61
Factory New

ABB, Manual Motor Starter, Compact 45 mm wide magnetic-only, 20 A rated operational current, Designed for fuse-free short-circuit protection, manual switching, and reliable control of single- and three-phase electric load

Representative image shown
Product Details
SKU:
MO132-20
UPC:
4013614400285
Weight:
0.68 LBS
Width:
1.77 in
Height:
3.85 in
Depth:
3.41 in
Rated Operational Voltage:
600 V AC
Number of Poles:
3 Poles
Terminal Type:
Screw Terminals
Current Range:
16.0 A to 20.0 A

Complete Your Build
verified Verified fit These products are compatible with the

Auxiliary Contacts
Signaling Contacts
Shunt Trips
Undervoltage Releases
Busbars
Terminal Blocks
Enclosures
Shafts

Build My Enclosure

Total price: $0

Description

Description

The MO132-20 manual motor starter magnetic only is a compact 45 mm width device with a rated operational current of Ie = 20.0 A. This device is used to manually switch on and off loads/motors and to protect them reliably and without the need for a fuse from short-circuits. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 100 kA at 400 V AC. A combination together with overload relays or motor controllers allows the protection of motors. Further features are the built-in disconnect function, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter magnetic only is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks are available as accessory.

Specifications

Specifications

Technical

 
Rated Service Short-Circuit Breaking Capacity (Ics):
(230 V AC) 100 kA
(400 V AC) 100 kA
(440 V AC) 20 kA
(500 V AC) 20 kA
(690 V AC) 3 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(230 V AC) 100 kA
(400 V AC) 100 kA
(440 V AC) 20 kA
(500 V AC) 20 kA
(690 V AC) 3 kA
Rated Instantaneous Short-Circuit Current Setting (Ii): 250 A
Setting Range: None
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 7.5 kW
Rated Operational Power AC-3e (Pe): (400 V) Three Phase 7.5 kW
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 20 A
Rated Operational Current AC-3 (Ie): 20 A
Rated Operational Current AC-3e (Ie): 20 A
Rated Frequency (f):
Main Circuit 50 Hz
Main Circuit 60 Hz
Operating Frequency (fsw): 0 ... 400 Hz
Rated Impulse Withstand Voltage (Uimp): Main Circuit 6 kV
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 2.1 W
Number of Poles: 3P
Conventional Free-air Thermal Current (Ith): Main Circuit 20 A
Degree of Protection:
Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 50000 cycle
Mechanical Durability: Nr. Operations 100000 cycle
Terminal Type: Screw Terminals
Connecting Capacity Main Circuit:
Flexible with Ferrule 1/2x 0.75 ... 6 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 6 mm²
Flexible 1/2x 1 ... 2.5 mm²
Flexible 1/2x 2.5 ... 6 mm²
Rigid 1/2x 1 ... 2.5 mm²
Rigid 1/2x 2.5 ... 6 mm²
Tightening Torque: Main Circuit 2 N·m
Wire Stripping Length: Main Circuit 10 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: 1 ... 6
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance:
Electrical Conductive Board, Horizontal - Up to 400 V 0 mm
Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
Contact Position Indication: ON / OFF / TRIP
Standards:
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
IEC 60335-2-40 A2L
Remarks: For overload protection of the motors, an appropriate thermal or electronic overload relays must be used

Technical UL/CSA

 
Short-Circuit Current Rating (SCCR):
Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 35 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 35 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 30 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 18 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 30 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA
Maximum Operating Voltage UL/CSA: Main Circuit 600 V AC
Horsepower Rating UL/CSA:
(200 V AC) Three Phase 5 Hp
(208 V AC) Three Phase 5 Hp
(220 ... 240 V AC) Three Phase 5 Hp
(440 ... 480 V AC) Three Phase 10 Hp
(550 ... 600 V AC) Three Phase 15 Hp
Full Load Amps Motor Use:
(200 V AC) Three Phase 17.5 A
(208 V AC) Three Phase 16.7 A
(220 ... 240 V AC) Three Phase 15.2 A
(440 ... 480 V AC) Three Phase 14 A
(550 ... 600 V AC) Three Phase 17 A
Locked Rotor Amps:
(200 V AC) Three Phase 105.8 A
(208 V AC) Three Phase 102 A
(220 ... 240 V AC) Three Phase 92 A
(440 ... 480 V AC) Three Phase 81 A
(550 ... 600 V AC) Three Phase 93 A
General Use Rating UL/CSA: (600 V AC) 20 A
Connecting Capacity Main Circuit UL/CSA:
Flexible 1/2x 16-8 AWG
Stranded 1/2x 16-8 AWG
Tightening Torque UL/CSA: Main Circuit 18 in·lb

Environmental

 
Ambient Air Temperature:
Around the Enclosure 0 ... +40 °C
Operation -25 ... +60 °C
Storage -50 ... +80 °C
Ambient Air Temperature Compensation: No
Maximum Operating Altitude Permissible: 2000 m
Resistance to Shock acc. to IEC 60068-2-27: 11 ms Pulse 25g
Resistance to Vibrations: 5g 3 ... 150 Hz