What Is a Load Reactor and When Does Your VFD Need One?

Nov 17th 2026

load reactors,

A load reactor is an inductor installed on the output side of a variable frequency drive (VFD), between the drive and the motor, to protect the motor from the voltage stress the drive’s output creates. It’s also called an output reactor. Whether your drive needs one depends mostly on the motor and the cable run between it and the drive, and on what the drive manufacturer specifies for that combination.

Say you’re replacing a starter with a VFD and keeping the existing motor. The horsepower and voltage match, but the motor was built to run on utility power. Before you commission it, check how the motor will handle the drive’s switching waveform and whether the cable run calls for a reactor or more output filtering.

Load Reactor vs Line Reactor

The name tells you where the reactor goes. A line reactor sits between the supply and the drive. A load reactor sits on the motor side, in series with the VFD output. Both add inductance, but each acts on a different part of the circuit.

A line reactor protects the drive and the power supply. A load reactor protects the motor and the cable by limiting rapid changes in current on the motor circuit and can reduce the severity of voltage transients seen by the motor. An input reactor doesn’t provide that motor-side function.

Some line reactors, including the TCI KDR series, are rated for use on either side of a VFD. Ask Wistex to confirm the specific unit’s output rating and application guidance before you specify it. The two positions expose the reactor to different waveforms.

How a Load Reactor Works

Many PWM AC drives use IGBTs to switch the DC bus into a series of pulses. The motor responds to the fundamental component, but the pulse edges still reach the motor cable. At the motor terminals, the difference between cable and motor impedance can reflect those fast edges back along the cable. The incident and reflected waves can combine, producing a peak voltage well above the drive’s rated output voltage.

A load reactor adds series impedance that slows the rate of current change and smooths the output waveform. That reduces stress on the motor insulation, and it can also lower motor heating and the audible noise caused by the drive waveform.

The result depends on the drive, cable and motor. A reactor doesn’t convert the PWM output into a sine wave or guarantee a particular peak voltage at the motor terminals.

Signs Your VFD Needs a Load Reactor

Start with the motor nameplate, the drive manual and the actual cable route. The distance between the two enclosures isn’t necessarily the cable length once you account for the route through tray, conduit or machinery.

Consider a load reactor in these situations:

  • A motor cable runs up to 100 feet where reflected waves are a concern. Use that distance as a starting point, then check the drive’s guidance for your voltage, carrier frequency and motor insulation.
  • An older or non-inverter-duty motor on a new drive. Confirm whether the motor is suitable for PWM service. An output reactor can help reduce stress, but it can’t make an unsuitable motor compatible.
  • A motor that runs hotter or sounds different on the drive. Check loading, cooling at low speed, drive settings and mechanical condition before attributing the symptom to PWM. A reactor may help if output ripple is part of the problem.
  • Several motors on one drive. Review the cable branches, combined current and protection for each motor. Ask Wistex whether the arrangement calls for a common output device or a different approach.

A short run to an inverter-duty motor often needs no separate reactor when the drive and motor documentation supports that setup.

When a Load Reactor Is Not Enough: dV/dt Filters

For runs beyond 100 feet, consider a dV/dt filter. Suitable applications can reach up to 3,000 feet, but that is an application-dependent upper limit. The drive voltage, carrier frequency, cable characteristics and motor requirements determine the allowable run for the actual equipment.

A dV/dt filter combines inductance with a damping network to slow the voltage rise time and limit peak voltage at the motor terminals. That’s a different job from adding series inductance alone. If the concern is repeated insulation stress from steep edges and reflected peaks, select a device based on the motor-terminal conditions it’s designed to achieve.

TCI’s V1K series is an example of a dV/dt output filter. Check its documentation and confirm the cable length it supports with your drive before treating 3,000 feet as a design allowance. For the longest runs, or where the motor needs a waveform close to a true sine wave, a sine wave filter is the highest level of output filtering. 

Choosing a Load Reactor

Size the reactor for the complete drive and motor circuit. Horsepower can help you find a starting point in a selection table, but it doesn’t account for every motor or duty cycle.

  1. Match the voltage and output application. Confirm the reactor is rated for the system voltage and PWM output.
  2. Check the current. Compare the motor nameplate full-load amps, the drive’s rated output and the expected overload duty. For multiple motors, check the combined load and the manufacturer’s sizing method.
  3. Select impedance for the circuit. A 3% reactor is the general-purpose choice for the output side. The 5% option applies to input reactors, where harmonic mitigation is the priority, so don’t assume higher impedance is the answer to a motor-side voltage problem.
  4. Choose the construction and mounting. Check whether you need an open or enclosed unit, then verify clearances, ventilation and placement in the manufacturer’s instructions.

Then check the manufacturer’s selection tables for the voltage, current and impedance combination, and have qualified personnel confirm the selection and installation against the drive and reactor documentation before commissioning.

Trade-Offs to Know

A reactor takes up panel space, generates heat and introduces voltage drop under load. More impedance generally means more voltage drop, which leaves less voltage available to the motor. That can matter where the application already needs most of the available motor voltage to deliver rated performance.

Consider the panel and the motor together. If space or ventilation is limited, include the reactor’s losses in the thermal plan. If the drive and motor manufacturers already support the cable run without added filtering, determine what problem a reactor would solve before adding one.

Common Questions About Load Reactors

These questions clarify what an output reactor does and where it belongs. Use the equipment manuals for the limits and wiring details of a specific installation.

What is the purpose of a load reactor?

A load reactor protects a motor from the voltage stress created by a VFD’s output. It adds inductance between the drive and motor, limiting rapid changes in output current and reducing insulation stress. A dV/dt filter may be more appropriate when motor-terminal voltage peaks are the primary concern.

Can you use a line reactor as a load reactor?

Yes, if the manufacturer rates that exact reactor for VFD output use. Some product families, including TCI KDR, support input and output applications. Check the voltage, current, overload duty and PWM application guidance. A reactor intended only for the supply side should not be assumed suitable for the motor circuit.

Does a load reactor go before or after the VFD?

A load reactor goes after the VFD, electrically between the drive’s output terminals and the motor. It’s installed in series with the motor circuit. The physical mounting location and permissible wiring between the drive and reactor depend on the manufacturer’s instructions, so confirm both when laying out the panel.

What does dV/dt mean?

dV/dt is the rate at which voltage changes over time. At the output of a PWM drive, it describes how steeply voltage rises or falls at a switching edge. A dV/dt filter slows those edges and limits motor-terminal voltage peaks under the operating conditions for which it’s rated.

Check the Drive, Motor and Cable Together

Contact Wistex with the drive horsepower and voltage, motor full-load amps and actual motor cable length for help choosing a load reactor or dV/dt filter. If you have them, include the drive model, carrier frequency and motor insulation rating. Those details help narrow the selection before you commit panel space or order a component.