Representative image shown

PSR45-600-70

Soft Starter (45 Amps)

$768.07
Factory New
Representative image shown
Product Details
SKU:
PSR45-600-70
UPC:
7320500338346
Weight:
2.50 LBS
Series:
PSR
Amperage:
45 Amps
Voltage:
208 - 600V AC

Specifications

Specifications

Dimensions

 
Product Net Width: 54 mm
Product Net Height: 187 mm
Product Net Depth / Length: 153 mm
Product Net Weight: 1 kg

Technical

 
Rated Operational Voltage: 208 ... 600 V AC
Rated Control Supply Voltage (Us): 100 ... 240 V AC
Rated Control Circuit Voltage (Uc): 24 V DC
Rated Frequency (f): 50/60 Hz
Main Circuit 50 / 60 Hz
Rated Operational Power - In-Line Connection (Pe): (230 V) 11 kW
(400 V) 22 kW
(500 V) 30 kW
Rated Operational Current - In-Line Connection (Ie): 45 A
Service Factor Percentage: 100 %
Overload Protection: Recommended MS450 36 ... 45
Integrated Electronic Overload: No
Starting Capacity at Maximum Rated Current Ie: 4xIe for 6s
Ramp Time:
0 ... 20 s
1 ... 10 s
Initial Voltage During Start:
40 ... 70 %
Step Down Voltage Special Ramp:
100 ... 60 %
Current Limit Function: No
Switch for Inside Delta Connection: No
Run Signal Relay: Yes
By-pass Signal Relay: Yes
Fault Signal Relay: No
Overload Signal Relay: No
Signal indication completed start ramp (LED): Green
Signal indication ready to start/standby ON (LED): Green
Signal indication running R (LED): Green
Signal indication ramping up/down (LED): Green
Number of Starts Per Hour at 3.5*Ie for 7 sec. 50% ON Time 50% OFF Time: 10
Communication: FiledBusPlug(Optional)
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type: Screw Terminals
Connecting Capacity Main Circuit:
Rigid 1x 6 ... 35 mm²
Rigid 2 x 6 ... 16 mm²
Connecting Capacity Control Circuit:
1 x 0.75 ... 2.5 mm²
2 x 0.75 ... 2.5 mm²
Rigid 1 x 0.75 ... 2.5 mm²
Rigid 2 x 0.75 ... 1.5 mm²
Connecting Capacity Supply Circuit:
Rigid 1 x 0.75 ... 2.5
Tightening Torque: Control Circuit 0.6 N·m
Main Circuit 4 N·m
Supply Circuit 0.6 N·m
Product Main Type: PSR45
Function:
Soft start with voltage ramp
Soft stop with voltage ramp

Technical UL/CSA

 
Horsepower Rating UL/CSA:
(200 ... 208 V AC) Three Phase 15 Hp
(220 ... 240 V AC) Three Phase 15 Hp
(440 ... 480 V AC) Three Phase 30 Hp
(550 ... 600 V AC) Three Phase 45 Hp
Maximum Operating Voltage UL/CSA:
Main Circuit 600 V
Tightening Torque UL/CSA:
Control Circuit 5.3 in·lb
Main Circuit 35.4
Supply Circuit 5.3 in·lb

Environmental

 
Ambient Air Temperature:
Operation -25 ... +60 °C
Storage -40 ... +70 °C