Specifications
Specifications
Dimensions |
|
|---|---|
| Product Net Width: | 90 mm |
| Product Net Height: | 245 mm |
| Product Net Depth / Length: | 184 mm |
| Product Net Weight: | 2.5 kg |
Technical |
|
| Rated Operational Voltage: | 208 ... 600 V AC |
| Rated Control Supply Voltage (Us): | 100 ... 250 V AC |
| Rated Control Circuit Voltage (Uc): | 24 V DC |
| Rated Frequency (f): | 50/60 Hz Main Circuit 50 / 60 Hz |
| Rated Operational Power - In-Line Connection (Pe): | (230 V) 9 kW (400 V) 18.5 kW (500 V) 22 kW |
| Rated Operational Current - In-Line Connection (Ie): | 37 A |
| Service Factor Percentage: | 100 % |
| Overload Protection: | Build-in electronic overload protection |
| Integrated Electronic Overload: | Yes |
| Starting Capacity at Maximum Rated Current Ie: | 4xIe for 10s |
| Ramp Time: |
0 ... 30 s
1 ... 30 s
|
| Initial Voltage During Start: |
30 ... 70 %
|
| Step Down Voltage Special Ramp: |
No %
|
| Current Limit Function: | 1.5 ... 7xIe |
| Switch for Inside Delta Connection: | No |
| Run Signal Relay: | Yes |
| By-pass Signal Relay: | Yes |
| Fault Signal Relay: | Yes |
| Overload Signal Relay: | Yes |
| Analog Outputs: | 4...20 mA |
| Signal indication completed start ramp (LED): | Green |
| Signal indication ready to start/standby ON (LED): | Green |
| Signal indication running R (LED): | Green |
| Signal indication ramping up/down (LED): | Green |
| Signal Indication Protection (LED): | Yellow |
|
Signal Indication Fault (LED):
|
Red |
| Number of Starts Per Hour at 3.5*Ie for 7 sec. 50% ON Time 50% OFF Time: | 10 |
| Communication: |
Modbus-RTU
|
| Degree of Protection: |
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
|
| Terminal Type: | Screw Terminals |
| Connecting Capacity Main Circuit: |
Hole Diameter 8.5 mm
Rigid 1/2 x 2.5 ... 70 mm²
Width and Thickness 17.5x5 mm
|
|
Connecting Capacity Control Circuit:
|
Rigid 1 x 2.5 mm²
Rigid 2 x 1.5 mm²
|
| Connecting Capacity Supply Circuit: |
Rigid 1 x 2.5
|
| Tightening Torque: |
Control Circuit 0.5 N·m
Main Circuit 9 N·m
Supply Circuit 0.5 N·m
|
| Product Main Type: | PSE37 |
| Function: |
Soft start with torque control
Soft start with voltage ramp
Soft stop with torque control
Soft stop with voltage ramp
Kick start
Sequence start
Current limit
Start reverse (external contactors)
Automatic restart
Event log
|
| Protection Function: |
Electronic overload protection, EOL; Locked rotor protection; Current underload protection
|
Technical UL/CSA |
|
| Horsepower Rating UL/CSA: |
(200 ... 208 V AC) Three Phase 10 Hp
(220 ... 240 V AC) Three Phase 10 Hp
(440 ... 480 V AC) Three Phase 25 Hp
(550 ... 600 V AC) Three Phase 30 Hp
|
|
Maximum Operating Voltage UL/CSA:
|
Main Circuit 600 V
|
| Tightening Torque UL/CSA: |
Control Circuit 4.4 in·lb
Main Circuit 79.7
Supply Circuit 4.4 in·lb
|
Environmental |
|
|
Ambient Air Temperature:
|
Operation -25 ... +60 °C
Storage -40 ... +70 °C
|