MS165 is a compact and powerful range for motor protection up to 45 kW (400 V) / 80 A in width of 55 mm. They offer a reliable protection for motors in the event of overload or phase failure. The devices have trip class 10.
This type also has a clear and reliable indication of fault in a separate window in the event of short-circuit tripping. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter (also known as motor protection circuit breaker or manual motor protector) is suitable for three- and single phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, under-voltage releases, shunt trips, power in-feed blocks are available as accessory. These are suitable throughout the MS116/MS132/MS165 range.
Specifications
Dimensions |
|
---|---|
Product Net Width | 55 mm |
Product Net Height | 142.65 mm |
Product Net Depth / Length | 122 mm |
Technical |
|
Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 30 kA (250 V DC) 3 Poles in Series 100 kA (400 V AC) 30 kA (440 V AC) 18 kA (500 V AC) 10 kA (690 V AC) 6 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 30 kA (250 V DC) 100 kA (400 V AC) 30 kA (440 V AC) 18 kA (500 V AC) 10 kA (690 V AC) 8 kA |
Rated Instantaneous Short-Circuit Current Setting (Ii) | 1022 A |
Setting Range | 62 ... 73 A |
Rated Operational Power AC-3 (Pe) | (400 V) Three Phase 37 kW |
Rated Operational Power AC-3e (Pe) | (400 V) Three Phase 37 kW |
Rated Operational Voltage | Main Circuit 690 V AC Main Circuit 250 V DC |
Rated Operational Current (Ie) | 73 A |
Rated Operational Current AC-3 (Ie) | 73 A |
Rated Operational Current AC-3e (Ie) | 73 A |
Rated Operational Current DC-5 (Ie) | 73 A |
Rated Frequency (f) | Main Circuit 50 Hz Main Circuit 60 Hz |
Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kV |
Rated Insulation Voltage (Ui) | 1000 V |
Power Loss | at Rated Operating Conditions per Pole 5.22 W |
Number of Poles | 3 |
Conventional Free-air Thermal Current (Ith) | Main Circuit 73 A |
Degree of Protection | Housing IP20 Main Circuit Terminals IP10 |
Pollution Degree | 3 |
Electrical Durability | 20000 cycle |
Mechanical Durability | 50000 cycle |
Terminal Type | Screw Terminals |
Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 1 ... 35 mm² Flexible with Insulated Ferrule 1/2x 1 ... 35 mm² Flexible 1/2x 1 ... 35 mm² Rigid 1/2x 1 ... 4 mm² Solid 1/2x 1 ... 4 mm² Stranded 1/2x 1 ... 50 mm² |
Tightening Torque | Main Circuit 4 N·m |
Wire Stripping Length | Main Circuit 16 mm |
Recommended Screw Driver | Pozidriv 2 |
Mounting Position | 1 ... 6 |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Minimum Mounting Distance | Electrical Conductive Board, Horizontal - Up to 1000 V 1.5 mm Electrical Conductive Board, Horizontal - Up to 400 V 0 mm Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm Electrical Conductive Board, Vertical 75 mm Other Device Same Type, Horizontal 0 mm Other Device Same Type, Vertical 150 mm |
Actuator Type | Rotary Handle |
Contact Position Indication | ON / OFF / TRIP |