- SKU:
- MS165-73
- UPC:
- 4013614536625
- Weight:
- 2.43 LBS
- Width:
- 2.17 in
- Height:
- 5.62 in
- Depth:
- 4.80 in
- Current Range:
- 62 - 73 Amperage
- Voltage:
- 600V AC
- Number of Poles:
- 3 Pole
- Trip Class:
- 10
MS165-73
Manual Motor Starter ( 62 - 73 A)
$516.70
Factory New
ABB
ABB, Manual Motor Starter, 55 mm wide, 73 A, providing overload, short-circuit, and phase-failure protection for electric motors up to 37 kW / 60 hp, featuring trip class 10 and a lockable rotary handle
Representative image shown
Product Details
Complete Your Build
verified
Verified fit
These products are compatible with the
Auxiliary Contacts
Signaling Contacts
Shunt Trips
Undervoltage Releases
Busbars
Shafts
Build My Enclosure
Total price: $0
Description
Description
MS165 is a compact and powerful range for motor protection up to 45 kW (400 V) / 80 A in width of 55 mm. They offer a reliable protection for motors in the event of overload or phase failure. The devices have trip class 10.
This type also has a clear and reliable indication of fault in a separate window in the event of short-circuit tripping. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter (also known as motor protection circuit breaker or manual motor protector) is suitable for three- and single phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, under-voltage releases, shunt trips, power in-feed blocks are available as accessory. These are suitable throughout the MS116/MS132/MS165 range.
This type also has a clear and reliable indication of fault in a separate window in the event of short-circuit tripping. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter (also known as motor protection circuit breaker or manual motor protector) is suitable for three- and single phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, under-voltage releases, shunt trips, power in-feed blocks are available as accessory. These are suitable throughout the MS116/MS132/MS165 range.
Specifications
Specifications
Technical |
|
| Rated Service Short-Circuit Breaking Capacity (Ics): |
(230 V AC) 30 kA
(250 V DC) 3 Poles in Series 100 kA
(400 V AC) 30 kA
(440 V AC) 18 kA
(500 V AC) 10 kA
(690 V AC) 6 kA
|
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): |
(230 V AC) 30 kA
(250 V DC) 100 kA
(400 V AC) 30 kA
(440 V AC) 18 kA
(500 V AC) 10 kA
(690 V AC) 8 kA
|
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 1022 A |
| Setting Range: | 62 ... 73 A |
| Rated Operational Power AC-3 (Pe): | (400 V) Three Phase 37 kW |
| Rated Operational Power AC-3e (Pe): | (400 V) Three Phase 37 kW |
| Rated Operational Voltage: |
Main Circuit 690 V AC
Main Circuit 250 V DC
|
| Rated Operational Current (Ie): | 73 A |
| Rated Operational Current AC-3 (Ie): | 73 A |
| Rated Operational Current AC-3e (Ie): | 73 A |
| Rated Operational Current DC-5 (Ie): | 73 A |
| Rated Frequency (f): |
Main Circuit 50 Hz
Main Circuit 60 Hz
|
| Operating Frequency (fsw): | 0 ... 415 Hz |
| Rated Impulse Withstand Voltage (Uimp): | Main Circuit 8 kV |
| Rated Insulation Voltage (Ui): | 1000 V |
| Power Loss: | at Rated Operating Conditions per Pole 5.22 ... 6.92 W |
| Number of Poles: | 3P |
| Conventional Free-air Thermal Current (Ith): | Main Circuit 73 A |
| Degree of Protection: |
Housing IP20
Main Circuit Terminals IP10
|
| Pollution Degree: | 3 |
| Electrical Durability: | 20000 cycle |
| Mechanical Durability: | Nr. Operations 50000 cycle |
| Terminal Type: | Screw Terminals |
| Connecting Capacity Main Circuit: |
Flexible with Ferrule 1/2x 1 ... 35 mm²
Flexible with Insulated Ferrule 1/2x 1 ... 35 mm²
Flexible 1/2x 1 ... 35 mm²
Rigid 1/2x 1 ... 4 mm²
Solid 1/2x 1 ... 4 mm²
Stranded 1/2x 1 ... 50 mm²
|
| Tightening Torque: | Main Circuit 4 N·m |
| Wire Stripping Length: | Main Circuit 16 mm |
| Recommended Screw Driver: | Pozidriv 2 |
| Mounting Position: | 1 ... 6 |
| Mounting on DIN Rail: |
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
|
| Minimum Mounting Distance: |
Electrical Conductive Board, Horizontal - Up to 1000 V 1.5 mm
Electrical Conductive Board, Horizontal - Up to 400 V 0 mm
Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
|
| Contact Position Indication: | ON / OFF / TRIP |
| Standards: |
CSA 22.2 No. 14
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-4-1
|
Technical UL/CSA |
|
| Short-Circuit Current Rating (SCCR): |
Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 50 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 50 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 10 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 50 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 10 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 50 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 10 kA
|
| Maximum Operating Voltage UL/CSA: | Main Circuit 600 V AC |
| Horsepower Rating UL/CSA: |
(200 V AC) Three Phase 20 Hp
(208 V AC) Three Phase 20 Hp
(220 ... 240 V AC) Three Phase 25 Hp
(440 ... 480 V AC) Three Phase 50 Hp
(550 ... 600 V AC) Three Phase 60 Hp
|
| Full Load Amps Motor Use: |
(110 ... 120 V AC) Three Phase 56 A
(200 V AC) Three Phase 62.1 A
(208 V AC) Three Phase 59.4 A
(220 ... 240 V AC) Three Phase 68 A
(440 ... 480 V AC) Three Phase 65 A
(550 ... 600 V AC) Three Phase 62 A
|
| Locked Rotor Amps: |
(200 V AC) Three Phase 334 A
(208 V AC) Three Phase 321 A
(220 ... 240 V AC) Three Phase 365 A
(440 ... 480 V AC) Three Phase 363 A
(550 ... 600 V AC) Three Phase 348 A
|
| General Use Rating UL/CSA: | (600 V AC) 73 A |
| Connecting Capacity Main Circuit UL/CSA: |
Flexible 1/2x 16-0 AWG
Stranded 1/2x 16-0 AWG
|
| Tightening Torque UL/CSA: | Main Circuit 35 in·lb |
Environmental |
|
| Ambient Air Temperature: |
Operation -25 ... +70 °C
Operation Compensated -25 ... +60 °C
Storage -50 ... +80 °C
|
| Ambient Air Temperature Compensation: | Yes |
| Maximum Operating Altitude Permissible: | 2000 m |
| Resistance to Shock acc. to IEC 60068-2-27: | 11 ms Pulse 25g |
| Resistance to Vibrations: |
Mounted on Mounting Plate: 5g 3 ... 150 Hz
Mounted on DIN-Rail: 4g 3 ... 150 Hz
|