Representative image shown

MS165-73

Manual Motor Starter ( 62 - 73 A)

$516.70
Factory New

ABB, Manual Motor Starter, 55 mm wide, 73 A, providing overload, short-circuit, and phase-failure protection for electric motors up to 37 kW / 60 hp, featuring trip class 10 and a lockable rotary handle

Representative image shown
Product Details
SKU:
MS165-73
UPC:
4013614536625
Weight:
2.43 LBS
Width:
2.17 in
Height:
5.62 in
Depth:
4.80 in
Current Range:
62 - 73 Amperage
Voltage:
600V AC
Number of Poles:
3 Pole
Trip Class:
10

Complete Your Build
verified Verified fit These products are compatible with the

Auxiliary Contacts
Signaling Contacts
Shunt Trips
Undervoltage Releases
Busbars
Shafts

Build My Enclosure

Total price: $0

Description

Description
MS165 is a compact and powerful range for motor protection up to 45 kW (400 V) / 80 A in width of 55 mm. They offer a reliable protection for motors in the event of overload or phase failure. The devices have trip class 10.
This type also has a clear and reliable indication of fault in a separate window in the event of short-circuit tripping. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter (also known as motor protection circuit breaker or manual motor protector) is suitable for three- and single phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, under-voltage releases, shunt trips, power in-feed blocks are available as accessory. These are suitable throughout the MS116/MS132/MS165 range.

Specifications

Specifications
 

Technical

 
 Rated Service Short-Circuit Breaking Capacity (Ics):  
(230 V AC) 30 kA
(250 V DC) 3 Poles in Series 100 kA
(400 V AC) 30 kA
(440 V AC) 18 kA
(500 V AC) 10 kA
(690 V AC) 6 kA
 Rated Ultimate Short-Circuit Breaking Capacity (Icu):  
(230 V AC) 30 kA
(250 V DC) 100 kA
(400 V AC) 30 kA
(440 V AC) 18 kA
(500 V AC) 10 kA
(690 V AC) 8 kA
 Rated Instantaneous Short-Circuit Current Setting (Ii):  1022 A
 Setting Range:  62 ... 73 A
 Rated Operational Power AC-3 (Pe):  (400 V) Three Phase 37 kW
 Rated Operational Power AC-3e (Pe):  (400 V) Three Phase 37 kW
 Rated Operational Voltage:  
Main Circuit 690 V AC
Main Circuit 250 V DC
 Rated Operational Current (Ie):  73 A
 Rated Operational Current AC-3 (Ie):  73 A
 Rated Operational Current AC-3e (Ie):  73 A
 Rated Operational Current DC-5 (Ie):  73 A
 Rated Frequency (f):  
Main Circuit 50 Hz
Main Circuit 60 Hz
 Operating Frequency (fsw):  0 ... 415 Hz
 Rated Impulse Withstand Voltage (Uimp):  Main Circuit 8 kV
 Rated Insulation Voltage (Ui):  1000 V
 Power Loss:  at Rated Operating Conditions per Pole 5.22 ... 6.92 W
 Number of Poles:  3P
 Conventional Free-air Thermal Current (Ith):  Main Circuit 73 A
 Degree of Protection:  
Housing IP20
Main Circuit Terminals IP10
 Pollution Degree:  3
 Electrical Durability:  20000 cycle
 Mechanical Durability:  Nr. Operations 50000 cycle
 Terminal Type:  Screw Terminals
 Connecting Capacity Main Circuit:  
Flexible with Ferrule 1/2x 1 ... 35 mm²
Flexible with Insulated Ferrule 1/2x 1 ... 35 mm²
Flexible 1/2x 1 ... 35 mm²
Rigid 1/2x 1 ... 4 mm²
Solid 1/2x 1 ... 4 mm²
Stranded 1/2x 1 ... 50 mm²
 Tightening Torque:  Main Circuit 4 N·m
 Wire Stripping Length:  Main Circuit 16 mm
 Recommended Screw Driver:  Pozidriv 2
 Mounting Position:  1 ... 6
 Mounting on DIN Rail:  
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
 Minimum Mounting Distance:
Electrical Conductive Board, Horizontal - Up to 1000 V 1.5 mm
Electrical Conductive Board, Horizontal - Up to 400 V 0 mm
Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
 
 Contact Position Indication:  ON / OFF / TRIP
 Standards:  
CSA 22.2 No. 14
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-4-1
 

Technical UL/CSA

 
 Short-Circuit Current Rating (SCCR):  
Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 50 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 50 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 10 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 50 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 10 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 50 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 10 kA
 Maximum Operating Voltage UL/CSA:  Main Circuit 600 V AC
 Horsepower Rating UL/CSA:  
(200 V AC) Three Phase 20 Hp
(208 V AC) Three Phase 20 Hp
(220 ... 240 V AC) Three Phase 25 Hp
(440 ... 480 V AC) Three Phase 50 Hp
(550 ... 600 V AC) Three Phase 60 Hp
 Full Load Amps Motor Use:  
(110 ... 120 V AC) Three Phase 56 A
(200 V AC) Three Phase 62.1 A
(208 V AC) Three Phase 59.4 A
(220 ... 240 V AC) Three Phase 68 A
(440 ... 480 V AC) Three Phase 65 A
(550 ... 600 V AC) Three Phase 62 A
 Locked Rotor Amps:  
(200 V AC) Three Phase 334 A
(208 V AC) Three Phase 321 A
(220 ... 240 V AC) Three Phase 365 A
(440 ... 480 V AC) Three Phase 363 A
(550 ... 600 V AC) Three Phase 348 A
 General Use Rating UL/CSA:  (600 V AC) 73 A
 Connecting Capacity Main Circuit UL/CSA:  
Flexible 1/2x 16-0 AWG
Stranded 1/2x 16-0 AWG
 Tightening Torque UL/CSA:  Main Circuit 35 in·lb
 

Environmental

 
 Ambient Air Temperature:  
Operation -25 ... +70 °C
Operation Compensated -25 ... +60 °C
Storage -50 ... +80 °C
 Ambient Air Temperature Compensation:  Yes
 Maximum Operating Altitude Permissible:  2000 m
 Resistance to Shock acc. to IEC 60068-2-27:  11 ms Pulse 25g
 Resistance to Vibrations:  
Mounted on Mounting Plate: 5g 3 ... 150 Hz
Mounted on DIN-Rail: 4g 3 ... 150 Hz