Description
The HF-ROLE-range is our safety range with emergency stop function. It's used for the direct-on-line start of motors and the switching of non-resistive loads. With contactor and overload relay functionalities integrated into one device, the results are faster wiring times and fewer faults. The range covers 0.6 A, 2.4 A and up to 9 A - for motors up to 3 kW – 500 V AC. The integrated electronic overload protection has a wide setting range that enables just three models to cover all requirements. Setting range of HF2.4-ROLE-24VDC is 0.18 A to 2.4 A. The control supply voltage is 24 V DC. For the control and main connection points ABB offers screw connections. Safety Integrity Level 3 in accordance with functional safety standard IEC 61508-1 and Performance Level 'e' in accordance with ISO 13849-1 are certified. Also ATEX is certified.
Specifications
Technical |
|
| Standards: |
IEC/EN 60947-1
IEC/EN 60947-4-2
IEC/EN 61508
IS0 13849
UL 60947-1
UL 60947-4-2
|
| Function: | Reversed-on-line starter with electronic overload protection and emergency stop function |
| Utilization: | Motor Protection |
| Rated Operational Voltage: | Main Circuit 500 V AC |
| Operational Voltage: |
Maximum 550 V AC
Minimum 42 V AC
|
| Rated Frequency (f): |
Main Circuit 50 Hz
Main Circuit 60 Hz
|
| Rated Control Supply Voltage (Us): | 24 V DC |
| Rated Input Voltage (UIN): |
Switching Threshold at Signal <0> -3 ... 9.6 V
Switching Threshold at Signal <1> 19.2 ... 30 V
|
| Rated Impulse Withstand Voltage (Uimp): | Main Circuit 6 kV |
| Rated Insulation Voltage (Ui): | 500 V |
| Rated Operational Current AC-51 (Ie): | 2.4 A |
| Rated Operational Current AC-53a (Ie): | 2.4 A |
| Rated Control Supply Current (Is): | 0.04 A |
| Rated Uninterrupted Current (Iu): | 2.4 A |
| Input Current: | 0.003 A |
| Switching Frequency: |
≤ 2 Hz
120 starts/min
7200 starts/h
|
| Rated Operational Power AC-53a (Pe): | 0.75 kW |
| Overvoltage Category: | III |
| Overload Protection: | Electronic overload protection |
| Setting Range: | 0.18 ... 2.4 A |
| Trip Class: | class 10A |
| Number of Poles: | 3P |
| Power Loss: |
Maximum 3.3 W
Minimum 1.1 W
|
| Number of Protected Poles: | 3 |
| Mechanical Durability: | Nr. Operations 10000 cycle |
| Electrical Durability: | 30000000 cycle |
| Delay Time (τ): |
Off, Maximum, Switched Off via Control Input Voltage 40 ms
Off, Maximum, Switched Off via Supply Voltage 500 ms
Off, Typical, Switched Off via Control Input Voltage 30 ms
Off, Typical, Switched Off via Supply Voltage 25 ms
Off, Maximum, Switched Off with Pushbutton 3 s
Off, Minimum, Switched Off with Pushbutton 0.5 s
|
| Mounting on DIN Rail: |
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
|
| Mounting Position: | 1 |
| Connecting Capacity Control Circuit: |
Flexible with Ferrule 1/2x 1 ... 2.5 mm²
Flexible 1/2x 1 ... 2.5 mm²
Rigid 1x 0.5 ... 4 mm²
|
| Connecting Capacity Main Circuit: |
Flexible with Ferrule 1x 2 ... 2.5 mm²
Flexible 1x 2 ... 2.5 mm²
Rigid 1x 2 ... 2.5 mm²
|
| Recommended Screw Driver: |
Control Circuit M3
Main Circuit M3
|
| Terminal Type: | Screw Terminals |
| Tightening Torque: |
Control Circuit 0.5 ... 0.6 N·m
Main Circuit 0.5 ... 0.6 N·m
|
| Wire Stripping Length: |
Control Circuit 8 mm
Main Circuit 8 mm
|
| Response Time: |
Phase Asymmetry 33% 120 s
Phase Asymmetry 67% 1.8 s
Phase Failure 1.8 s
|
| Pollution Degree: | 2 |
| Phase Loss Sensitive: | Yes |
| Degree of Protection: |
Housing IP20
Main Circuit Terminals IP20
|
| Short-Circuit Current Rating (SCCR): | (500 V AC, 30 A Class J or CC) 100 kA |
Technical UL/CSA |
|
| Maximum Operating Voltage UL/CSA: | Main Circuit 500 V AC |
| Horsepower Rating UL/CSA: |
Nominal Switching Performance Full Load (power factor = 0.4) 1.2 Hp
Nominal Switching Performance Full Load (power factor = 0.8) 2.2 Hp
|
| Full Load Amps Motor Use: | 2.4 A |
| Connecting Capacity Main Circuit UL/CSA: |
Flexible with Ferrule 1x 24 ... 14 AWG
Flexible 1x 24 ... 14 AWG
Solid 1x 24 ... 14 AWG
|
| Connecting Capacity Control Circuit UL/CSA: |
Flexible with Ferrule 1x 24 ... 14 AWG
Flexible 16-8 AWG
Solid 1x 24 ... 14 AWG
|
| Tightening Torque UL/CSA: |
Control Circuit 5 ... 7 in·lb
Main Circuit 5 ... 7 in·lb
|
Safety Information |
|
| Safety Integrity Level (SIL): | 3 |
| Safety Category: | 3 |
| Performance Level (PL): | Up to e |
| Mean Time to Dangerous Failure (MTTFd): |
Motor Protection 447 year
Safe Shutdown 517 year
|
| Mean Time to Failure (MTTF): | 39.3 year |
| Diagnostic Coverage: | 98.79 % |
| Diagnostic Coverage Safe (DCS): | 40.71 % |
Environmental |
|
| Ambient Air Temperature: |
Operation -25 ... +70 °C
Operation Compensated -40 ... + 80 °C
|
| Maximum Operating Altitude Permissible: | Without Derating 2000 m |