Representative image shown

Ex9QR50376D

Soft Starters (37 Amps, 200-690 VAC, 25 HP)

$970.52
Factory New

Electronic soft-starter - NOARK (Ex9QR5 series) - 37A rated current - 200Vac-690Vac rated input voltage - 100Vac-240Vac control voltage - 22kW (460Vac; mtr. rating; IEC) / 25HP (480Vac; mtr. rating; UL) rated power

Representative image shown
Product Details
SKU:
Ex9QR50376D
Weight:
5.00 LBS
Series:
Ex9QR5
Rated Current:
37 Amps
Rated Input Voltage:
200 - 690V AC
Control Voltage:
100 - 240V AC
Horsepower:
25 HP

Specifications

Specifications
Main function Soft starter
Product series / family name Industrial controls > Soft starters
Sub-range name
Ex9QR5 series
Functions Electronic soft-starter
Built-in signal relays (K1) -- Bypass relay
Built-in signal relays (K2) -- Programmable status relay
Built-in signal relays (K3) -- Programmable fault relay
Optional I/O (IN1) -- Programmable input terminal
Optional I/O (IN2) -- Programmable input terminal
Cooling fan
Design
Without bypass contactor
Supply voltage (AC) 200-690 V AC
Frequency
35-60Hz (current mode)
48-52Hz (other starting mode)
58-62Hz (other starting mode)
Display LCD display
Rated current
37A
32A (200Vac; motor rating FLA; UL)
31A (208Vac; motor rating FLA; UL)
28A (240Vac; motor rating FLA; UL)
34A (480Vac; motor rating FLA; UL)
30A (600Vac; motor rating FLA; UL)
36A (220Vac; motor rating FLA; IEC)
36A (380Vac; motor rating FLA; IEC)
36A (460Vac; motor rating FLA; IEC)
36A (575Vac; motor rating FLA; IEC)
36A (690Vac; motor rating FLA; IEC)
Rated active power (kW)
22kW (460Vac; mtr. rating; IEC)
11kW (220Vac; motor rating; IEC)
18.5kW (380Vac; motor rating; IEC)
30kW (575Vac; motor rating; IEC)
30kW (690Vac; motor rating; IEC)
Rated power (HP)
25HP (480Vac; mtr. rating; UL)
10HP (200Vac; motor rating; UL)
10HP (208Vac; motor rating; UL)
10HP (240Vac; motor rating; UL)
32HP (600Vac; motor rating; UL)
Rated operating voltage (Ue)
(AC) 60-483 V
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
800 V
Connection type
Built-in lugs (power connections)
M3 screw connection (control circuit)
Cross-section #14AWG...#6AWG / 2.5mm2...16mm2 lugs
#13AWG control circuit conductors
Short circuit breaking rating
5 kA (UL/IEC)
Control Voltage (AC)
100-240 V AC
Protection functions
Overload protection (classes 10A; 10; 20; 30)
Phase loss/phase unbalance
Starting current limit timeout
Undervoltage/Overvoltage
Output phase loss
Motor overload
Load locked/short circuit
Multi-start lockout
Communication protocol
RS-485
Modbus
Digital inputs
1 x digital input (Start; NO dry contact)
1 x digital input (Stop; NC dry contact)
1 x digital input (Emergency Stop; NC dry contact)
Analog inputs
1 x analog input (PTC thermistor input; optional I/O)
Dimensions (H x W x D)
264.5 mm x 184 mm x 165.3 mm
10.4 in x 7.2 in x 6.5 in
Ambient air temperature for operation
 -14°F...+104°F / -10°C...+40 °C
Ambient air temperature for storage
 -13°F...+158°F / -25°C...+70 °C
Technical compatibility with
Recommended protection -- M1S100T3L MCCB or 125A 600V K5 fuse
Bypass -- Ex9C40F11K contactor
Application type
<1000m above sea level -- full performance
1000-3000m above sea level -- the current derated 0.5% for every 100m
Order code / Manufacturer SKU
Ex9QR5-37-6-D
1720003
Ex9QR50376D
Manufacturer product status
Commercialized
Equivalent to
1720003
Ex9QR50376D
Ex9QR5376D
Compliant with standard(s)
UL 508 (file number E533416)
UL 60947-4-2
CSA C22.2 No. 14
CSA C22.2 No. 60947-4-2
Shock resistance -- less than 0.5g
EMC equipment level -- Class A (industrial grade) Level 3
Tightening torque
(screw) 5 N.m
(control circuit) 0.5 N.m
Degree of pollution
Class III

Benefits

Benefits

Ex9QR5 is a solid-state reduced voltage (SSRV) motor starter used in the control and protection of 3-phase electric motors.
Its multiple starting modes control the voltage and current applied to the motor to provide soft start‚ speed ramp and soft stop capability.
The Ex9QR5 has built-in motor overload protection in class 10‚ 20 and 30‚ along with advanced protection such as phase loss/phase unbalance‚ under-voltage and more.
It is the ideal solution for energy savings and torque control in applications like fans‚ blowers‚ pumps‚ compressors‚ ball mills‚ crushers and many other loads.

Features

Features
  • Seven unique starting modes
  • Automatic light-load energy savings
  • Low-speed forward and reverse
  • Programmable kickstart mode
  • Soft stop and braking
  • Sequential‚ multiple motor starting
  • Programmable digital inputs and analog output
  • Built-in RS-485 communication interface and standard Modbus protocol
  • Separately mountable LCD display with user-friendly interface

Motor Protection Functions

Motor Protection Functions
  • Phase loss/phase unbalance
  • Starting current limit timeout
  • Undervoltage/Overvoltage
  • Output phase loss
  • Motor overload
  • Load locked/short circuit
  • Multi-start lockout