MS132-6.3

Manual Motor Starter (4.0-6.3A)

$153.68
Factory New

ABB, Manual Motor Starter, 45 mm wide, adjustable current range of 4.0 to 6.3 A, provides fuse-less protection against overloads, short circuits, and phase failures for single- and three-phase applications up to 690 VAC

Representative image shown
Product Details
SKU:
MS132-6.3
UPC:
4013614400094
Weight:
0.62 LBS
Width:
1.77 in
Height:
3.54 in
Depth:
3.42 in
Current Range:
4.0 A to 6.3 A
Number of Poles:
3 Pole
Trip Class:
Class 10

Complete Your Build
verified Verified fit These products are compatible with the

Auxiliary Contacts
Signaling Contacts
Shunt Trips
Undervoltage Releases
Busbars
Terminal Blocks
Enclosures
Shafts

Build My Enclosure

Total price: $0

Description

Description

The MS132-6.3 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 6.3 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 100 kA at 400 VAC and trip class 10. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and terminal spacers are available as accessory.

Specifications

Specifications

Technical

 
Rated Service Short-Circuit Breaking Capacity (Ics):
(230 V AC) 100 kA
(250 V DC) 3 Poles in Series 10 kA
(400 V AC) 100 kA
(440 V AC) 30 kA
(500 V AC) 20 kA
(690 V AC) 3 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(230 V AC) 100 kA
(400 V AC) 100 kA
(440 V AC) 30 kA
(500 V AC) 20 kA
(690 V AC) 3 kA
Rated Instantaneous Short-Circuit Current Setting (Ii): 78.8 A
Setting Range: 4.0 ... 6.3 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 2.2 kW
Rated Operational Power AC-3e (Pe): (400 V) Three Phase 2.2 kW
Rated Operational Voltage:
Main Circuit 690 V AC
Main Circuit 250 V DC
Rated Operational Current (Ie): 6.3 A
Rated Operational Current AC-3 (Ie): 6.3 A
Rated Operational Current AC-3e (Ie): 6.3 A
Rated Operational Current DC-5 (Ie): 6.3 A
Rated Frequency (f):
Main Circuit 50 Hz
Main Circuit 60 Hz
Operating Frequency (fsw): 0 ... 400 Hz
Rated Impulse Withstand Voltage (Uimp): Main Circuit 6 kV
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 0.7 ... 1.8 W
Number of Poles: 3P
Conventional Free-air Thermal Current (Ith): Main Circuit 6.3 A
Degree of Protection:
Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 50000 cycle
Mechanical Durability: Nr. Operations 100000 cycle
Terminal Type: Screw Terminals
Connecting Capacity Main Circuit:
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque: Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Main Circuit 9 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: 1 ... 6
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance:
Electrical Conductive Board, Horizontal - Up to 400 V 0 mm
Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
Contact Position Indication: ON / OFF / TRIP
Standards:
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
IEC 60335-2-40 A2L
Remarks: UL508 Self-Protected Combination Motor Controller (Type E) in combination with feeder block S1-M3-xx

Technical UL/CSA

 
Short-Circuit Current Rating (SCCR):
Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 65 kA
Manual Self-Protected Combination Controllers (Type E), (600Y / 347 V AC) 18 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 35 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 18 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA
Maximum Operating Voltage UL/CSA:
Main Circuit 600 V AC
Horsepower Rating UL/CSA:
(200 V AC) Three Phase 1 Hp
(208 V AC) Three Phase 1 Hp
(220 ... 240 V AC) Three Phase 1.5 Hp
(440 ... 480 V AC) Three Phase 3 Hp
(550 ... 600 V AC) Three Phase 5 Hp
Full Load Amps Motor Use:
(200 V AC) Three Phase 6.3 A
(208 V AC) Three Phase 6.3 A
(220 ... 240 V AC) Three Phase 6.3 A
(440 ... 480 V AC) Three Phase 4.8 A
(550 ... 600 V AC) Three Phase 6.1 A
Locked Rotor Amps:
(200 V AC) Three Phase 37.8 A
(208 V AC) Three Phase 37.8 A
(220 ... 240 V AC) Three Phase 37.8 A
(440 ... 480 V AC) Three Phase 32 A
(550 ... 600 V AC) Three Phase 36.8 A
General Use Rating UL/CSA: (600 V AC) 6.3 A
Connecting Capacity Main Circuit UL/CSA:
Flexible 1/2x 16-12 AWG
Stranded 1/2x 16-12 AWG
Tightening Torque UL/CSA: Main Circuit 10 ... 12 in·lb

Environmental

 
Ambient Air Temperature:
Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +60 °C
Storage -50 ... +80 °C
Ambient Air Temperature Compensation: Yes
Maximum Operating Altitude Permissible: 2000 m
Resistance to Shock acc. to IEC 60068-2-27: 11 ms Pulse 25g
Resistance to Vibrations: 5g 3 ... 150 Hz