Representative image shown

MS132-0.16B

Manual Motor Starter (0.10-0.16A)

$181.05
Factory New

ABB, Manual Motor Starter, 0.10-0.16A, 45 mm, Designed for reliable switching and fuse-less protection of low-voltage motors

Representative image shown
Product Details
SKU:
MS132-0.16B
UPC:
4013614521317
Weight:
0.47 LBS
Width:
1.77 in
Height:
3.54 in
Depth:
3.42 in
Current Range:
0.10 to 0.16A
Number of Poles:
3 Poles
Terminal Type:
Screw Terminals
Trip Class:
Class 10A

Complete Your Build
verified Verified fit These products are compatible with the

Auxiliary Contacts
Signaling Contacts
Shunt Trips
Undervoltage Releases
Busbars
Terminal Blocks
Hardware
Enclosures
Mounting
Shafts

Build My Enclosure

Total price: $0

Description

Description

MS132-B is a compact and powerful range for motor protection up to 15 kW (400 V) / 32 A in width of 45 mm, complying with the latest railway rolling stock standards and allowing installation in passengers or driver cabins for trains frequently operating tunnels or undergrounds. They offer a reliable protection for motors in the event of overload or phase failure. The devices have trip class 10. This type has also a clear and reliable indication of fault in a separate window in the event of short-circuit tripping. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, power in-feed blocks are available as accessory. These are suitable throughout the MS132-B/MS165-B range.

– designed in accordance to the applicable parts of IEC 60077 standard

– shocks and vibration withstand conforming to IEC 61373 (category 1, class B)

– usable according to European fire and smoke safety standard EN 45545-2

Specifications

Specifications

Technical

 
Rated Service Short-Circuit Breaking Capacity (Ics):
(230 V AC) 100 kA
(250 V DC) 3 Poles in Series 10 kA
(400 V AC) 100 kA
(440 V AC) 100 kA
(500 V AC) 100 kA
(690 V AC) 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(230 V AC) 100 kA
(400 V AC) 100 kA
(440 V AC) 100 kA
(500 V AC) 100 kA
(690 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (Ii): 2 A
Setting Range: 0.10 ... 0.16 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 0.03 kW
Rated Operational Power AC-3e (Pe): (400 V) Three Phase 0.03 kW
Rated Operational Voltage:
Main Circuit 690 V AC
Main Circuit 250 V DC
Rated Operational Current (Ie): 0.16 A
Rated Operational Current AC-3 (Ie): 0.16 A
Rated Operational Current AC-3e (Ie): 0.16 A
Rated Operational Current DC-5 (Ie): 0.16 A
Rated Frequency (f):
Main Circuit 50 Hz
Main Circuit 60 Hz
Operating Frequency (fsw): 0 ... 400 Hz
Rated Impulse Withstand Voltage (Uimp): Main Circuit 6 kV
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 0.7 ... 1.7 W
Number of Poles: 3P
Conventional Free-air Thermal Current (Ith): Main Circuit 0.16 A
Degree of Protection:
Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 50000 cycle
Mechanical Durability: Nr. Operations 100000 cycle
Terminal Type: Screw Terminals
Connecting Capacity Main Circuit:
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque: Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Main Circuit 9 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: 1 ... 6
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance:
Electrical Conductive Board, Horizontal - Up to 400 V 0 mm
Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
Contact Position Indication: ON / OFF / TRIP
Standards:
IEC 60077-1 (applicable parts)
IEC 60077-2 (applicable parts)
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
Remarks: UL508 Self-Protected Combination Motor Controller (Type E) in combination with feeder block S1-M3-xx

Technical UL/CSA

 
Short-Circuit Current Rating (SCCR):
Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 65 kA
Manual Self-Protected Combination Controllers (Type E), (600Y / 347 V AC) 47 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 47 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 47 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA
Maximum Operating Voltage UL/CSA: Main Circuit 600 V AC
Full Load Amps Motor Use:
(200 V AC) Three Phase 0.16 A
(208 V AC) Three Phase 0.16 A
(220 ... 240 V AC) Three Phase 0.16 A
(440 ... 480 V AC) Three Phase 0.16 A
(550 ... 600 V AC) Three Phase 0.16 A
Locked Rotor Amps:
(200 V AC) Three Phase 0.96 A
(208 V AC) Three Phase 0.96 A
(220 ... 240 V AC) Three Phase 0.96 A
(440 ... 480 V AC) Three Phase 0.96 A
(550 ... 600 V AC) Three Phase 0.96 A
General Use Rating UL/CSA: (600 V AC) 0.16 A
Connecting Capacity Main Circuit UL/CSA:
Flexible 1/2x 16-12 AWG
Stranded 1/2x 16-12 AWG
Tightening Torque UL/CSA: Main Circuit 10 ... 12 in·lb

Environmental

 
Ambient Air Temperature:
Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +60 °C
Storage -50 ... +80 °C
Ambient Air Temperature Compensation: Yes
Maximum Operating Altitude Permissible: 2000 m
Resistance to Shock acc. to IEC 60068-2-27: 11 ms Pulse 25g
Resistance to Vibrations: 5g 3 ... 150 Hz
Shock and Vibration Withstand acc. to IEC 61373: Category 1, Class B