Representative image shown

Ex9S32A0.16A

Ex9S32 Manual Motor Starter (0.1-0.16 Amps)

$62.82
Factory New

Thermal-magnetic Manual Motor Starter (MMS) / Branch protector - NOARK (Ex9S32 series) - 0.1A...0.16A current setting range - Interrupting capacity 65kA (type E; 240Vac; 480Y/277Vac) - Rotary handle operation - 3-poles (3P)

Representative image shown
Product Details
SKU:
Ex9S32A0.16A
Weight:
5.00 LBS
Series:
Ex9S32
Rated Current:
0.1 - 0.16 Amps
Rated Impulse Voltage:
6 kV

Specifications

Specifications
Primary brand NOARK
Main function
Motor Protection Circuit Breaker (MPCB)
Product series / family name
Industrial controls > Manual Motor Starters (MMSs)
Sub-range name
Ex9S32 series
Network frequency
50/60 Hz
Functions
Thermal-magnetic Manual Motor Starter (MMS) / Branch protector
Poles
3-poles (3P)
Rated current
0.1A...0.16A current setting range
0.16A (conventional thermal current; Ith)
Frame current rating
32 AF
Rated active power (kW)
0.06kW (AC-3; 500Vac)
0.06kW (AC-3; 690Vac)
Rated operating voltage (Ue)
(AC) 230/240 V
(AC) 400/415 V
(AC) 460/480 V
(AC) 575/600 V
Rated impulse voltage (Uimp)
6 kV
Rated insulation voltage (Ui)
(IEC) 690 V
(UL/CSA) 600 V
Connection type
M4 slotted head screw connections
Cross-section
#14AWG / 2.5mm2 conductors
Short circuit breaking rating
65kA (type E; 240Vac; 480Y/277Vac)
10kA (type E; 600Y/347Vac)
65kA (type F; 240Vac; 480Y/277Vac)
10kA (type F; 600Y/347Vac)
Ultimate short circuit current breaking capacity (Icu)
100kA (400Vac)
100kA (690Vac)
Service short circuit current breaking capacity (Ics)
100kA (400Vac)
100kA (690Vac)
Trip unit type
Technology = Thermal-Magnetic (adjustable)
Protection functions
Adjustable thermal protection (Overload) Class 10
Fixed threshold magnetic protection (Short-circuit)
Phase failure protection
Protection settings
Protection against thermal overload -- 0.1A...0.16A (adjustable)
Magnetic instantaneous protection against short-circuit -- 2.1A
Operating mode
Rotary handle operation
Degree of protection
IP20
Dimensions
H3.83" x W1.77" x D3.84"
H97.3mm x W45mm x D97.5mm
Ambient air temperature for operation
-4...+140°F / -20...+60 °C
Ambient air temperature for storage
-4...+176°F / -40...+80 °C
Technical compatibility with
Ex9S32 mtr. starter
6-9A Ex9CS contactor
9A Ex9C contactor
Minimum current
0.1 A
Maximum current
0.16 A
Order code / Manufacturer SKU
Ex9S32A0.16A
1600046
Manufacturer product status
Commercialized
Equivalent to
Ex9S32A016A
1600046
Compliant with standard(s)
Vibration resistance - 5-150Hz with 5gn
Shock resistance - 30gn for 11ms
UL 60947-4-1
UL 60947-1
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
IEC/EN 60947-5-1
RoHS
CCC
NOM
CSA 22.2 No. 60947-1
CSA 22.2 No. 60947-4-1
GB/T 14048.1
GB/T 14048.2
GB/T 14048.4
Class 10
Operating rate
max. 30 Cycles/hour
Tightening torque
2.5 N.m
Degree of pollution
III
Application type
2000m / 6562ft max. operating altitude

Benefits

Benefits
Ex9S Manual Motor Starter provide manual isolation‚ manual motor control‚ and over-current protection.
Ex9S Manual Motor Starters are electro-mechanical devices combining the functions below in one unit.

- Disconnect for Motor Branch Circuit
- Manual Motor Control (automatic when used with contactor)
- Branch-Circuit Short Circuit Protection (Magnetic Protection)
- Overload Protection (Thermal Protection) - Trip Class 10
- 5-year limited warranty

The National Electrical Codes requires an individual Motor Branch Circuit to be protected by a UL/CSA Listed Fuse‚ Circuit breaker or Self-Protected Combination Motor Controller.

Available asː
- Up to 80A at 600Vac
- UL 60947-4-1 Type E Self Protection-Ex9S32 and Ex9S80
- UL 60947-4-1 Type F Group Motor Protection-Ex9S80
- Built-in fault indication
- Full range of accessories
- Lockable handle