Description
The DRAF09-11S is an enclosed Direct-On-Line starter with an AF contactor used for controlling 3-phase asynchronous motors up to 690 V AC. Each starter is delivered assembled and wired.
It contains:
• IP66 and type 4X plastic enclosure with double insulation, equiped with: - 1 green flush "I" ON button and 1 red protruding "O" OFF/RESET button - 4 cable inlets and outlets via knockouts: mm cable inlet/outlet suitable for IEC starter types.
• 1 AF09-30-10-11 3-pole contactor with holding contact
• DRAF..S with separate supply: - AC control supply: 24-60V50/60HZ - DC control supply: 24...60 V DC
• 1 CB5-10 start contact block
• 1 PE and 1 neutral terminal
• TF42 thermal overload relay to be ordered separately and chosen according to motor's nominal current
Specifications
Technical |
|
| Coil Consumption: | Holding at Max. Rated Control Circuit Voltage 60 Hz 24 V·A |
|
Connecting Capacity Auxiliary Circuit:
|
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid Solid 1/2x 1 ... 2.5 mm²
Rigid Stranded 1/2x 1 ... 2.5 mm²
|
| Connecting Capacity Control Circuit: |
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 1.5 mm²
Rigid Solid 1/2x 1 ... 2.5 mm²
Rigid Stranded 1/2x 1 ... 2.5 mm²
|
| Connecting Capacity Main Circuit: |
Flexible with Ferrule 1/2x 0.75 ... 6 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 4 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Rigid Solid 1/2x 1 ... 4 mm²
Rigid Stranded 1/2x 1 ... 6 mm²
|
| Housing Material: | ABS |
| Number of Auxiliary Contacts NC: | 0 |
| Number of Auxiliary Contacts NO: | 1 |
| Number of Main Contacts NC: | 0 |
| Number of Main Contacts NO: | 3 |
| Number of Poles: | 3P |
| Pollution Degree: | 3 |
| Rated Control Circuit Voltage (Uc): |
50 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation 20 ... 60 V
|
| Rated Frequency (f): |
Auxiliary Circuit 50 / 60 Hz
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
|
| Rated Insulation Voltage (Ui): |
acc. to IEC 60947-4-1 690 V
acc. to IEC 60947-5-1 690 V
|
| Rated Operational Current AC-1 (Ie): |
690 V) 40 °C 25 A
(690 V) 60 °C 25 A
(690 V) 70 °C 22 A
|
| Rated Operational Current AC-3 (Ie): |
(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
(380 / 400 V) 60 °C 9 A
(220 / 230 / 240 V) 60 °C 9 A
|
| Rated Operational Current AC-3e (Ie): |
(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
(380 / 400 V) 60 °C 9 A
(220 / 230 / 240 V) 60 °C 9 A
|
| Rated Operational Power AC-3 (Pe): |
(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
(380 / 400 V) 4 kW
(220 / 230 / 240 V) 2.2 kW
|
| Rated Operational Power AC-3e (Pe): |
(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
(380 / 400 V) 4 kW
(220 / 230 / 240 V) 2.2 kW
|
| Terminal Type: | Screw Terminals |
Technical UL/CSA |
|
| Pilot Duty UL/CSA: |
A600
Q600
|