The B6-30-01-P mini contactor is a compact 3 pole contactor with 1 auxiliary contact and soldering pins. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 4 kW (AC-3) and 12 A (AC-1) or switching of control signals. Further features are the silent coil, a switch position indication and the integrated possibility for rail mounting.
Specifications
Specifications
| Product Net Width | 47.5 mm |
|---|---|
| Product Net Depth / Length | 47.7 mm |
| Product Net Height | 45.2 mm |
| Product Net Weight | 0.17 kg |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 3P |
| Standards |
IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
UL 60947-1
UL 60947-4-1
IEC 60335-2-40 A2L
|
| Rated Operational Voltage |
Auxiliary Circuit 690 V AC
Auxiliary Circuit 250 V DC
Main Circuit 690 V AC
Main Circuit 220 V DC
|
| Rated Frequency (f) |
Control Circuit 400 Hz
Control Circuit 50 Hz
Control Circuit 60 Hz
Main Circuit 50 Hz
Main Circuit 60 Hz
Main Circuit DC
|
| Conventional Free-air Thermal Current (Ith) |
Main Circuit 12 A
|
| Rated Operational Current AC-1 (Ie) |
(220 / 240 V) 40 °C 12 A
(220 / 240 V) 55 °C 12 A
(380 / 440 V) 40 °C 12 A
(380 / 440 V) 55 °C 12 A
(690 V) 40 °C 6 A
(690 V) 55 °C 6 A
|
| Rated Operational Current AC-3 (Ie) |
(230 V) 55°C 9 A
(400 V) 55 °C 9 A
(500 V) 55 °C 6.5 A
(690 V) NO 55°C 3.5 A
|
| Rated Operational Current AC-15 (Ie) |
(24 V) 4 A
(120 V) 4 A
(500 V) 2 A
(220 / 240 V) 4 A
(380 / 400 V) 3 A
|
| Rated Operational Current DC-13 (Ie) |
(24 V) 2.5 A
(110 V) 0.7 A
(220 / 240 V) 0.4 A
|
| Rated Operational Power AC-3 (Pe) |
(230 V) Three Phase 2.2 kW
(400 V) Three Phase 4 kW
(500 V) Three Phase 4 kW
(690 V) Three Phase, NO 3 kW
|
| Rated Breaking Capacity AC-3 |
8 x Ie / AC-3
|
| Rated Making Capacity AC-3 |
10 x Ie / AC-3
|
| Rated Short-time Withstand Current Low Voltage (Icw) |
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A
|
| Rated Insulation Voltage (Ui) |
690 V
acc. to UL/CSA 600 V
|
| Rated Impulse Withstand Voltage (Uimp) |
Auxiliary Circuit 6 kV
Main Circuit 6 kV
|
| Maximum Electrical Switching Frequency |
(AC-1) 300 cycles per hour
(AC-15) 600 cycles per hour
(AC-3) 600 cycles per hour
(DC-1) 600 cycles per hour
(DC-13) 600 cycles per hour
(DC-3) 600 cycles per hour
|
| Mechanical Durability |
Nr. Operations 10000000 cycle
|
| Minimum Switching Capacity |
Auxiliary Circuit 17 V
Auxiliary Circuit 5 mA
|
| Coil Operating Limits |
(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
|
| Rated Control Circuit Voltage (Uc) |
24 V AC
|
| Coil Consumption |
Average Holding Value 50 Hz 3.5 V·A
Average Pull-in Value 50 Hz 3.5 V·A
|
| Power Loss |
at Rated Operating Conditions AC-1 per Pole 1 W
|
| Mounting on DIN Rail |
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
|
| Degree of Protection |
Auxiliary Circuit Terminals IP20
Control Circuit Terminals IP20
Main Circuit Terminals IP20
|
| Terminal Type |
Soldering Pins
|
| Mini Contactor Type |
Mini Contactor
|
| Product Name |
Mini Contactor
|
| Maximum Operating Voltage UL/CSA |
Main Circuit 600 V AC
|
| General Use Rating UL/CSA |
(300 V AC) 8 A
|
| Horsepower Rating UL/CSA |
(115 V AC) Single Phase 0.25 Hp
(200 V AC) Three Phase 1 Hp
(220 ... 240 V AC) Three Phase 2 Hp
(230 V AC) Single Phase 0.5 Hp
(440 ... 480 V AC) Three Phase 3 Hp
(550 ... 600 V AC) Three Phase 1 Hp
|
| Contact Rating UL/CSA |
A600
|
| Full Load Amps Motor Use |
(115 V AC) Single Phase 5.8 A
(200 V AC) Three Phase 4.8 A
(220 ... 240 V AC) Three Phase 6.8 A
(230 V AC) Single Phase 4.9 A
(440 ... 480 V AC) Three Phase 4.8 A
(550 ... 600 V AC) Three Phase 1.7 A
|
| Ambient Air Temperature |
Operation -25 ... +55 °C
Storage -40 ... +80 °C
|
| Maximum Operating Altitude Permissible |
2000 m
|
| Resistance to Shock acc. to IEC 60068-2-27 |
11 ms Pulse 15g
|
| Resistance to Vibrations |
5g 5 ... 150 Hz
|