Representative image shown

B6-30-01-P01

Mini Contactor (24 VAC, 3 NO, 0 NC)

$66.67
Factory New

The B6-30-01-P mini contactor is a compact 3 pole contactor with 1 auxiliary contact and soldering pins.

Representative image shown
Product Details
SKU:
B6-30-01-P01
UPC:
4013614051548
Weight:
0.37 LBS
Width:
1.87 in
Height:
1.78 in
Depth:
1.88 in

The B6-30-01-P mini contactor is a compact 3 pole contactor with 1 auxiliary contact and soldering pins. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 4 kW (AC-3) and 12 A (AC-1) or switching of control signals. Further features are the silent coil, a switch position indication and the integrated possibility for rail mounting.

Specifications

Specifications
Product Net Width 47.5 mm
Product Net Depth / Length 47.7 mm
Product Net Height 45.2 mm
Product Net Weight 0.17 kg
Number of Main Contacts NO 3
Number of Main Contacts NC 0
Number of Auxiliary Contacts NO 0
Number of Auxiliary Contacts NC 1
Number of Poles 3P
Standards
IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
UL 60947-1
UL 60947-4-1
IEC 60335-2-40 A2L
Rated Operational Voltage
Auxiliary Circuit 690 V AC
Auxiliary Circuit 250 V DC
Main Circuit 690 V AC
Main Circuit 220 V DC
Rated Frequency (f)
Control Circuit 400 Hz
Control Circuit 50 Hz
Control Circuit 60 Hz
Main Circuit 50 Hz
Main Circuit 60 Hz
Main Circuit DC
Conventional Free-air Thermal Current (Ith)
Main Circuit 12 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 12 A
(220 / 240 V) 55 °C 12 A
(380 / 440 V) 40 °C 12 A
(380 / 440 V) 55 °C 12 A
(690 V) 40 °C 6 A
(690 V) 55 °C 6 A
Rated Operational Current AC-3 (Ie)
(230 V) 55°C 9 A
(400 V) 55 °C 9 A
(500 V) 55 °C 6.5 A
(690 V) NO 55°C 3.5 A
Rated Operational Current AC-15 (Ie)
(24 V) 4 A
(120 V) 4 A
(500 V) 2 A
(220 / 240 V) 4 A
(380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A
(110 V) 0.7 A
(220 / 240 V) 0.4 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 2.2 kW
(400 V) Three Phase 4 kW
(500 V) Three Phase 4 kW
(690 V) Three Phase, NO 3 kW
Rated Breaking Capacity AC-3
8 x Ie / AC-3
Rated Making Capacity AC-3
10 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A
Rated Insulation Voltage (Ui)
690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Main Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour
(AC-15) 600 cycles per hour
(AC-3) 600 cycles per hour
(DC-1) 600 cycles per hour
(DC-13) 600 cycles per hour
(DC-3) 600 cycles per hour
Mechanical Durability
Nr. Operations 10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V
Auxiliary Circuit 5 mA
Coil Operating Limits
(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (Uc)
24 V AC
Coil Consumption
Average Holding Value 50 Hz 3.5 V·A
Average Pull-in Value 50 Hz 3.5 V·A
Power Loss
at Rated Operating Conditions AC-1 per Pole 1 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Degree of Protection
Auxiliary Circuit Terminals IP20
Control Circuit Terminals IP20
Main Circuit Terminals IP20
Terminal Type
Soldering Pins
Mini Contactor Type
Mini Contactor
Product Name
Mini Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
General Use Rating UL/CSA
(300 V AC) 8 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.25 Hp
(200 V AC) Three Phase 1 Hp
(220 ... 240 V AC) Three Phase 2 Hp
(230 V AC) Single Phase 0.5 Hp
(440 ... 480 V AC) Three Phase 3 Hp
(550 ... 600 V AC) Three Phase 1 Hp
Contact Rating UL/CSA
A600
Full Load Amps Motor Use
(115 V AC) Single Phase 5.8 A
(200 V AC) Three Phase 4.8 A
(220 ... 240 V AC) Three Phase 6.8 A
(230 V AC) Single Phase 4.9 A
(440 ... 480 V AC) Three Phase 4.8 A
(550 ... 600 V AC) Three Phase 1.7 A
Ambient Air Temperature
Operation -25 ... +55 °C
Storage -40 ... +80 °C
Maximum Operating Altitude Permissible
2000 m
Resistance to Shock acc. to IEC 60068-2-27
11 ms Pulse 15g
Resistance to Vibrations
5g 5 ... 150 Hz