Specifications
| Standards | CSA 22.2 No. 5 IEC/EN 60947-2 UL 489 |
|---|---|
| Tripping Characteristic | K |
| Rated Operational Voltage | acc. to IEC 60898-1 400 V AC acc. to IEC 60898-1 400 V acc. to IEC 60947-2 400 V AC |
| Rated Insulation Voltage (Ui) |
acc. to IEC/EN 60664-1 440 V
|
| Rated Impulse Withstand Voltage (Uimp) |
4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
|
| Dielectric Test Voltage | 50/60 Hz, 1 min: 2 kV |
| Input Voltage Type | AC/DC |
| Rated Current (In) | 50 A |
| Rated Short-Circuit Capacity | (400 V AC) 11.2 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) |
(400 V AC) 15 kA
(400 V) 15 kA
|
| Rated Conditional Short-Circuit Current (Inc) |
(400 V) 15 kA
|
| Rated Service Short-Circuit Breaking Capacity (Ics) |
(400 V AC) 7.5 kA
|
| Rated Frequency (f) |
50 / 60 Hz
DC
|
| Power Loss |
13.5 W
at Rated Operating Conditions per Pole 4.5 W
|
| Power Supply Connection |
Arbitrary
|
| Contact Position Indication |
Red ON / Green OFF
|
| Energy Limiting Class |
3
|
| Electrical Endurance |
10000 AC cycle
|
| Mechanical Endurance |
20000 cycle
|
| Number of Protected Poles |
3
|
| Number of Poles |
3
|
| Overvoltage Category |
III
|
| Tightening Torque |
2.8 N·m
|
| Screw Terminal Type |
Failsafe Bi-directional Cylinder-lift Terminal
|
| Actuator Marking |
I / O
|
| Actuator Material |
Insulation Group II, Black, Sealable
|
| Housing Material |
Insulation Group I, RAL 7035
|
| Mounting on DIN Rail |
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
|
| Mounting Position |
Any
|
| Recommended Screw Driver |
Pozidriv 2
|
| Accessories Available |
Yes
|
| Connecting Capacity |
Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
|
| Installation Size |
acc. to DIN 43880 3
|
| Terminal Type |
Double Clamp
|