Features
SU202MR-K60 ABB Miniature Circuit Breaker (10kA, 60A, 2P)
ABB MCBs are built to last. We achieve this through an uncompromising commitment to quality. ABB uses only the best components and materials. All materials comply with EU (RoHS, REACH) standards for sustainability and are halogen-free. Every unit is inspected three times before it leaves ABB facilities.
Terminal
Extended size with insulation for IP20 protection and new pressure plate for improved conductor connection — easier to handle, safer to use
Switching Mechanism
New design and assembly increases reliability of triggering — even under tough conditions
Contact Design
With a trip-free snap-action mechanism for improved arc movement and safe, optimized switching
Tripping Device
Optimized arc extinguishing system improves safety
Patented IP20 Finger-Safe Terminals
Extended size with insulation for IP20 protection and new pressure plate for improved conductor connection available for the S200 series. Additionally, our innovative ring-lug terminals are available (SU200MR and S200MR). MCBs of the S800U series are equipped with a convertible lug or ring-lug terminal.
Contact Position Indication
All System pro M compact MCBs are equipped with real contact position indication (CPI). This allows for quick identification of the MCB’s state, on or off, if maintenance is required. Working together, both the position of the toggle and the color of the CPI offer clear indication of the MCB’s contact position, providing additional safety. If an event has occurred, the MCB provides reliable information on its state.
Approvals Printed on the Dome
SU200M MCBs comply with UL489/CSA 22.2 No. 5 and carry approvals for other relevant markets or segments in which they may be used. For ease of identification, certification markings are printed on the dome and side of the MCB.
Comfort Connection
Dedicated busbars are available, depending on the application. The new cut-to-length UL Vario busbar is available for the SU200M. A special ring-lug busbar for the SU200MR and S200M was designed to fit these devices.
Maximum Flexibility
The dual terminals with two separate slots allow connection of busbars and cables in separate spots. They also allow for installation of up to four cables in each terminal (2+2).
Extra Power Needed?
S800 series MCBs offer high performance in terms of current, voltage and short circuit interrupt ratings.
Specifications
SU202MR-K60 ABB Miniature Circuit Breaker (10kA, 60A, 2P)
Width in Number of Modular Spacings | 2 |
---|---|
Product Net Width | 35 mm |
Product Net Height | 115 mm |
Product Net Depth / Length | 71 mm |
Product Net Weight | 0.28 kg |
Built-In Depth (t2) | 69 mm |
Standards | CSA 22.2 No. 5 IEC/EN 60947-2 UL 489 |
Tripping Characteristic | K |
Rated Operational Voltage | acc. to IEC 60898-1 400 V AC acc. to IEC 60947-2 400 V AC |
Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V |
Rated Impulse Withstand Voltage (Uimp) | 4 kV at 2000 m 5 kV at Sea Level 6.2 kV |
Input Voltage Type | AC |
Rated Current (In) | 60 A |
Rated Short-Circuit Capacity | (230 V AC) 10 kA (400 V AC) 10 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 10 kA (400 V AC) 15 kA |
Rated Conditional Short-Circuit Current (Inc) | (230 V) 10 kA (400 V) 10 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (400 V AC) 7.5 kA |
Rated Frequency (f) | 50 / 60 Hz |
Power Loss | 9.8 W at Rated Operating Conditions per Pole 4.9 W |
Energy Limiting Class | 3 |
Number of Poles | 2 |
Number of Protected Poles | 2 |
Overvoltage Category | III |
Screw Terminal Type | Ring-Tongue Terminal with Captive Screw |
Options Provided | Ring tongue |
Recommended Screw Driver | Pozidriv 2 |
Accessories Available | Yes |
Connecting Capacity | Flexible with Ferrule 0.75 ... 25 mm² Flexible 0.75 ... 25 mm² Rigid 0.75 ... 35 mm² Stranded 0.75 ... 35 mm² |
Terminal Type | Ring-Tongue Terminals |
Ambient Air Temperature | Operation -25 ... +55 °C |
Degree of Protection | IP20 |
Pollution Degree | 3 |
RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Interrupting Rating acc. to UL489 | (240 V AC) 10 kA (96 V DC) 10 kA |