- SKU:
- SU202M-K60
- UPC:
- 4016779932820
- Weight:
- 0.57 LBS
- Width:
- 1.38 in
- Height:
- 4.37 in
- Depth:
- 2.72 in
- Interrupting Rating:
- 10 kA
- Number of Poles:
- 2 Pole
- Amperage:
- 60 Amps
SU202M-K60
Miniature Circuit Breaker
$100.60
Factory New
ABB
Representative image shown
Product Details
Complete Your Build
verified
Verified fit
These products are compatible with the
Auxiliary Contacts
Shunt Trips
Build My Enclosure
Total price: $0
Description
Description
SU202M-K60 Miniature Circuit Breaker K-Char., UL10kA, IEC15kA, 60A, 2P UL489
Specifications
Specifications
Technical |
|
| Dielectric Test Voltage: | 50 / 60 Hz - 1 min 2 kV |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): |
(400 V AC) 15 kA
(400 V) 15 kA
|
| Rated Service Short-Circuit Breaking Capacity (Ics): | (400 V AC) 7.5 kA |
| Power Supply Connection: | Arbitrary |
| Contact Position Indication: | Red ON / Green OFF |
| Energy Limiting Class: | 3 |
| Electrical Endurance: | 10000 AC cycle |
| Mechanical Endurance: | 20000 cycle |
| Number of Protected Poles: | 2 |
| Number of Poles: | 2P |
| Tightening Torque: | 2.8 N·m |
| Screw Terminal Type: | Failsafe Bi-directional Cylinder-lift Terminal |
| Actuator Marking: | I / O |
| Actuator Material: | Insulation Group II, Black, Sealable |
| Recommended Screw Driver: | Pozidriv 2 |
| Accessories Available: | Yes |
| Connecting Capacity: |
Busbar 10/10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
|
| Installation Size: | acc. to DIN 43880 3 |
| Terminal Type: | Double Clamp |
| Actuator Type: | Toggle |
Electrical |
|
| Tripping Characteristic: | K |
| Rated Operational Voltage: | acc. to IEC 60947-2 400 V AC |
| Rated Insulation Voltage (Ui): | acc. to IEC/EN 60664-1 400 V |
| Rated Impulse Withstand Voltage (Uimp): |
4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
|
| Input Voltage Type: | AC/DC |
| Rated Current (In): | 60 A |
| Rated Short-Circuit Capacity: | (400 V AC) 11.2 kA |
| Rated Frequency (f): |
50 / 60 Hz
DC
|
| Power Loss: |
9.8 W
at Rated Operating Conditions per Pole 4.9 W
|
| Overvoltage Category: | III |
Design |
|
| Housing Material: | Insulation Group I, RAL 7035 |
Technical UL/CSA |
|
| Maximum Operating Voltage UL/CSA: |
240 V AC
96 V DC
|
| Interrupting Rating acc. to UL489: |
(240 V AC) 10 kA
(96 V DC) 10 kA
|
| Connecting Capacity UL/CSA: |
Busbar 18-8 AWG
Conductor 18-4 AWG
|
Environmental |
|
| Ambient Air Temperature: |
Operation -25 ... +55 °C
Storage -40 ... +70 °C
|
| Reference Ambient Air Temperature: | 30 °C |
| Degree of Protection: |
IP20
IP40
Enclosure with Cover IP40
|
| Pollution Degree: | 3 |
| Environmental Conditions: |
28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
|
| Resistance to Vibrations: | 20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz |
| Resistance to Shock acc. to IEC 60068-2-27: | 25g 2 shocks 13 ms |