Specifications
| Standards | CSA 22.2 No. 5 IEC/EN 60947-2 UL 489 |
|---|---|
| Product Name | Miniature Circuit Breaker |
| Tripping Characteristic | Z |
| Rated Operational Voltage | acc. to IEC 60898-1 277 V acc. to IEC 60947-2 230 V AC |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV at 2000 m 5 kV at Sea Level 6.2 kV |
| Dielectric Test Voltage | 50/60 Hz, 1 min: 2 kV |
| Input Voltage Type | AC/DC |
| Rated Current (In) | 5 A |
| Rated Short-Circuit Capacity (Icn) | (230 V AC) 11.2 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 15 kA |
| Rated Conditional Short-Circuit Current (Inc) | (230 V) 15 kA |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 11.2 kA |
| Rated Frequency (f) | 50 / 60 Hz DC |
| Power Loss | 1.8 W at Rated Operating Conditions per Pole 1.8 W |
| Power Supply Connection | Arbitrary |
| Contact Position Indication | Red ON / Green OFF |
| Energy Limiting Class | 3 |
| Electrical Endurance | 20000 AC cycle |
| Mechanical Endurance (Nendu) | 20000 cycle |
| Number of Poles | 1 |
| Number of Protected Poles | 1 |
| Overvoltage Category | III |
| Tightening Torque | 2.8 N·m |
| Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
| Actuator Marking | I / O |
| Actuator Material | Insulation Group II, Black, Sealable |
| Housing Material | Insulation Group I, RAL 7035 |
| Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Mounting Position | Any |
| Recommended Screw Driver | Pozidriv 2 |
| Accessories Available | Yes |
| Connecting Capacity | Busbar 10 / 10 mm² Flexible with Ferrule 0.75 ... 25 mm² Flexible 0.75 ... 25 mm² Rigid 0.75 ... 35 mm² Stranded 0.75 ... 35 mm² |
| Installation Size | acc. to DIN 43880 3 |
| Terminal Type | Double Clamp |