Specifications
Specifications
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (125 V DC) 15 kA (400 V AC) 15 kA (400 V) 15 kA |
|---|---|
| Rated Service Short-Circuit Breaking Capacity (Ics) | (400 V AC) 7.5 kA |
| Energy Limiting Class | 3 |
| Number of Protected Poles | 2 |
| Number of Poles | 2P |
| Accessories Available | Yes |
| Connecting Capacity | Flexible 25 ... 25 mm² Rigid 35 ... 35 mm² |
| Terminal Type | Double Clamp |
| Tripping Characteristic | Z |
| Rated Operational Voltage | acc. to IEC 60898-1 400 V acc. to IEC 60947-2 400 V AC |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 400 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Input Voltage Type | AC/DC |
| Rated Current (In) | 50 A |
| Rated Frequency (f) | 50 / 60 Hz |
| Power Loss | 2.5 W at Rated Operating Conditions per Pole 2.5 W |
| Overvoltage Category | III |
| Interrupting Rating acc. to UL1077 | (125 V DC) 10 kA (480Y / 277 V AC) 5 kA |
| Ambient Air Temperature | Operation -25 ... +55 °C |
| Degree of Protection | IP20 |
| Pollution Degree | 3 |
| Width in Number of Modular Spacings | 2 |
| Product Net Width | 35 mm |
| Product Net Height | 88 mm |
| Product Net Depth / Length | 69 mm |
| Product Net Weight | 0.24 kg |
| Built-In Depth (t2) | 69 mm |
| Standards | CSA 22.2 No. 235 IEC/EN 60947-2 UL 1077 |
| Certification Agency | CSA EN IEC UL |