Representative image shown

DC1-327D0NN-A20CE1

AC Variable Frequency Drive DC1 IP20 240V 3PH IN/3PH OUT 2HP, 7A ENH FW

$438.06
Factory New
Representative image shown
Product Details
SKU:
DC1-327D0NN-A20CE1
UPC:
786687020349
Weight:
2.90 LBS
Width:
5.00 in
Height:
6.25 in
Depth:
9.00 in
Series:
PowerXL DC1
NEMA Rating / Enclosure Type:
NEMA 1 (IP20)
Input Voltage (AC):
200 - 240V AC
Output Phase:
Three-phase
Horsepower:
2 HP
Amperage:
7 Amps
Bypass Option:
No
Request Repair

In-House Repair is available for this part.
Call 1-800-726-9307 to schedule your In-House Repair today.

Our Specialized Engineering Division also offers expertise in system modifications, retrofits, and advanced reengineering.

Request Repair

Specifications

Specifications
Product Name
Eaton DC1 Variable frequency drive
Catalog Number
185824
Product Length/Depth
124 mm
Product Height
184 mm
Product Width
81 mm
Product Weight
1.2 kg
Certifications
EAC
UL 508C
UkrSEPRO
UL Category Control No.: NMMS, NMMS7
UL
RCM
UL File No.: E172143
CE
CSA-C22.2 No. 14
Specification for general requirements: IEC/EN 61800-2
UL report applies to both US and Canada
IEC/EN61800-5
Safety requirements: IEC/EN 61800-5-1
Certified by UL for use in Canada
IEC/EN61800-3
CUL
RoHS, ISO 9001
IEC/EN 61800-3
Catalog Notes
Environmental class: 3C2, 3S2
Overload cycle for 60 s every 600 s
EAN
4015081813230
Model Code
DC1-327D0NN-A20CE1
Apparent power at 230 V
2.79 kVA
Apparent power at 240 V
2.91 kVA
Braking torque
Max. 100 % of rated operational current Ie, variable, DC - Main circuit
Max. 30 % MN, Standard - Main circuit
Altitude
Above 1000 m with 1 % derating per 100 m
Max. 4000 m
Ambient operating temperature - max
50 °C
Ambient storage temperature - max
60 °C
Ambient operating temperature - min
-10 °C
Ambient operating temperature at 150% overload - max
50 °C
Ambient operating temperature at 150% overload - min
-10 °C
Ambient storage temperature - min
-40 °C
Climatic proofing
< 95 average relative humidity (RH), no condensation, no corrosion
Number of inputs (analog)
2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
Number of inputs (digital)
4 (parameterizable, 10 - 30 V DC)
Number of outputs (analog)
1
Number of outputs (digital)
1
Number of relay outputs
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Equipment heat dissipation, current-dependent Pvid
61.5 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
7 A
Static heat dissipation, non-current-dependent Pvs
0 W
Features
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App)
Parameterization: Fieldbus
Parameterization: Keypad
Fitted with Internal DC link
IGBT inverter
Control unit
7-digital display assembly
PC connection
Additional PCB protection
Cable length 100 m, screened, with motor choke, maximum permissible, Motor feeder
150 m, unscreened, with motor choke, maximum permissible, Motor feeder
75 m, unscreened, maximum permissible, Motor feeder
50 m, screened, maximum permissible, Motor feeder
Communication interface SmartWire-DT, optional
OP-Bus (RS485), built in
CANopen®, built in
Modbus RTU, built in
Connection to SmartWire-DT In conjunction with DX-NET-SWD3 SmartWire DT module
Yes
Degree of protection IP20
NEMA Other
Frame size FS1
Mounting position Vertical
Product category Variable frequency drives
Protection Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
Protocol EtherNet/IP
CAN
MODBUS
Other bus systems
Radio interference class Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
Suitable for Branch circuits, (UL/CSA)
Efficiency 95.9 % (η)
Heat dissipation at current/speed 23 W at 25% current and 0% speed
27 W at 25% current and 50% speed
29 W at 50% current and 0% speed
37 W at 50% current and 50% speed
40 W at 50% current and 90% speed
54 W at 100% current and 0% speed
61 W at 100% current and 50% speed
70 W at 100% current and 90% speed
Input current ILN at 150% overload 9.5 A
Leakage current at ground IPE - max 7.5 mA
Mains switch-on frequency Maximum of one time every 30 seconds
Mains voltage - max 240 V
Mains voltage - min 200 V
Operating mode U/f control
Speed control with slip compensation
Sensorless vector control (SLV)
BLDC motors
PM motors
Synchronous reluctance motors
Output frequency - max 500 Hz
Output frequency - min 0 Hz
Output voltage (U2) 240 V AC, 3-phase
230 V AC, 3-phase
Overload current IL at 150% overload 10.5 A
Rated control supply voltage 10 V DC (Us, max. 10 mA)
Rated frequency - max 62 Hz
Rated frequency - min 48 Hz
Rated operational current (Ie) 7 A at 150% overload (at an operating frequency of 16 kHz and an ambient air temperature of +50 °C)
Rated operational voltage 240 V AC, 3-phase
230 V AC, 3-phase
Resolution 0.1 Hz (Frequency resolution, setpoint value)
Short-circuit protection rating 10 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
Starting current - max 175 %, IH, max. starting current (High Overload), For 2.5 seconds every 600 seconds, Power section
Supply frequency 50/60 Hz
Switching frequency 8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
System configuration type AC supply systems with earthed center point
Voltage rating - max 240 V
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload 6.8 A
Assigned motor current IM at 230 V, 50 Hz, 150% overload 6.3 A

Warranty Information

Manufacturer's Warranty: Eaton Selling Policy 25-000, one (1) year from the date of installation of the product or eighteen (18) months from the date of shipment of the product, whichever occurs first. Plus 5 years on capacitor cells.