The softstarter PSTX72-600-70 has a rated maximum operational current of 72 A with an operating voltage span from 208...600 V AC. The rated control voltage is between 100...250 V AC at 50/60 Hz. PSTX features a three-phase control soft start and stop through a voltage or a torque ramp. It has a built-in bypass for easy installation and energy saving. A RUN, TOR and Event signal is available from relay outputs in NO (normally open state). The PSTX has functions such as current limit, kickstart, analog output, EOL, motor heating and pump cleaning etc. To interact with PSTX, it has a detachable full graphic display with IP66 and 4x outdoor rating. There are four ways to communicate with PSTX. It can be done by hardwire inputs Start/Stop/Reset of fault, and by three programmable digital inputs. Another popular option is the built-in Fieldbus communication Modbus RTU and incl optional ANYBUS modules with every major protocol such as for example Profinet, Profibus, Modbus TCP, Ethernet IP and others. Another way to communicate with PSTX is to use an external adaptor and a Fieldbus plug. PSTX is the complete alternative for any motor starting application. It’s suitable for medium to large-sized three-phase motors with nominal currents from 30...1250 A inline connection or 52...2160 A inside delta connection. Typical applications are, for example, pumps, fans, compressors, and conveyors.
Specifications
Dimensions |
|
---|---|
Product Net Width | 150 mm |
Product Net Height | 314 mm |
Product Net Depth / Length | 198 mm |
Product Net Weight | 4.7 kg |
Technical |
|
Rated Operational Voltage | 208 ... 600 V AC |
Rated Control Supply Voltage (Us) | 100 ... 250 V AC |
Rated Control Circuit Voltage (Uc) | DC Operation 24 V |
Rated Frequency (f) | 50/60 Hz Main Circuit 50 / 60 Hz |
Rated Operational Power - In-Line Connection (Pe) | (230 V) 18.5 kW (400 V) 37 kW (500 V) 45 kW |
Rated Operational Current - In-Line Connection (Ie) | 72 A |
Rated Operational Power - Inside Delta Connection | at 230 V 37 kW at 400 V 59 kW at 500 V 80 kW |
Rated Operational Current - Inside Delta Connection | 124 A |
Service Factor Percentage | 100 % |
Overload Protection | Built-in electronic overload protection |
Integrated Electronic Overload | Yes |
Adjustable Rated Motor Current Ie | 30 ... 100 % |
Starting Capacity at Maximum Rated Current Ie | 4xIe for 10s |
Ramp Time | 1 ... 120 second [unit of time] |
Initial Voltage During Start | 10 ... 99 % |
Step Down Voltage Special Ramp | 100 ... 10 % |
Current Limit Function | 1.5 ... 7.5 xle |
Switch for Inside Delta Connection | Yes |
Run Signal Relay | Yes |
By-pass Signal Relay | Yes |
Fault Signal Relay | Yes |
Overload Signal Relay | Yes |
Analog Outputs | 0…10 V, 0…20 mA, 4…20 mA |
Signal indication ready to start/standby ON (LED) | Green |
Signal indication running R (LED) | Green |
Signal indication protection (LED) | Yellow |
Signal indication fault (LED) | Red |
Communication | Built in Modbus interface, Anybus, FieldBusPlug (with adapter) |
Degree of Protection | IP00 |
Terminal Type | Cable Clamp |
Connecting Capacity Main Circuit | Hole Diameter 8.5 mm |
Connecting Capacity Control Circuit | Rigid 1 x 2.5 mm² |
Connecting Capacity Supply Circuit | Rigid 1 x 2.5 mm² |
Tightening Torque | Main Circuit 8 N·m |
Product Main Type | PSTX72 |