TF42-16

Thermal Overload Relay (16 Amps, 690 V, 3 Pole)
Representative image shown

$42.46
$84.97
Product Condition: New
SKU:
TF42-16
UPC:
4013614398148
Weight:
0.29 LBS
Width:
1.77 in
Height:
3.48 in
Depth:
2.78 in
Setting Range:
13 - 16 Amps
Amperage:
16 Amps
Voltage:
690 V
Number of Poles:
3 Pole

The TF42-16 thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10. Further features are the temperature compensation, trip contact (NC), signal contact (NO), automatic- or manual reset selectable, trip-free mechanism, STOP function and a trip indication. The overload relays are connected directly to the block contactors. Single mounting kits are available as accessory.

Specifications - ABB TF42-16

Product Net Width 45 mm
Product Net Height 88.3 mm
Product Net Depth / Length 70.5 mm
Product Net Weight 0.13 kg
Setting Range 13 ... 16 A
Rated Operational Voltage Auxiliary Circuit 600 V AC/DC
Main Circuit 690 V AC
Main Circuit 600 V DC
Rated Operational Current (Ie) 16 A
Rated Frequency (f) Auxiliary Circuit 50 Hz
Auxiliary Circuit 60 Hz
Auxiliary Circuit DC
Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp) Auxiliary Circuit 6 kV
Main Circuit 6 kV
Rated Insulation Voltage (Ui) 690 V
Number of Poles 3
Number of Auxiliary Contacts NC 1
Number of Auxiliary Contacts NO 1
Number of Protected Poles 3
Conventional Free-air Thermal Current (Ith) Auxiliary Circuit NC 6 A
Auxiliary Circuit NO 4 A
Rated Operational Current AC-15 (Ie) (120 V) NC 3 A
(120 V) NO 0.5 A
(240 V) NC 3 A
(240 V) NO 0.5 A
(400 V) NC 0.75 A
(400 V) NO 0.5 A
(500 V) NC 0.75 A
(500 V) NO 0.5 A
Rated Operational Current DC-13 (Ie) (125 V) NC 0.55 A
(125 V) NO 0.55 A
(24 V) NC 1.25 A
(24 V) NO 1.25 A
(250 V) NC 0.27 A
(250 V) NO 0.27 A
(500 V) NC 0.15 A
(500 V) NO 0.15 A
(60 V) NC 0.55 A
(60 V) NO 0.55 A
Degree of Protection IP20
Pollution Degree 3
Connecting Capacity Auxiliary Circuit Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Flexible 1/2x 0.75 ... 1 mm²
Flexible 1/2x 1 ... 2.5 mm²
Rigid 1/2x 0.75 ... 4 mm²
Connecting Capacity Main Circuit Flexible with Ferrule 1/2x 0.75 ... 4 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 4 mm²
Flexible 1/2x 0.75 ... 4 mm²
Rigid 1/2x 0.75 ... 4 mm²
Tightening Torque Auxiliary Circuit 1 ... 1.2 N·m
Main Circuit 1.5 ... 2.5 N·m
Wire Stripping Length Auxiliary Circuit 9 mm
Main Circuit 12 mm
Recommended Screw Driver Main Circuit Pozidriv 2
Power Loss at Rated Operating Conditions per Pole 1.3 ... 2.2 W
Suitable For AF09
AF12
AF16
AF26
AF30
AF38
Standards IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
UL 60947-1
UL 60947-4-1
Maximum Operating Voltage UL/CSA Main Circuit 600 V AC
Contact Rating UL/CSA (NC:) B600
(NC:) Q600
(NO:) Q600
(NO:) D300
Connecting Capacity Main Circuit UL/CSA Flexible 1/2x 18-10 AWG
Stranded 1/2x 18-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA Flexible 1/2x 18-12 AWG
Stranded 1/2x 18-12 AWG
Tightening Torque UL/CSA Auxiliary Circuit 9 ... 11 in·lb
Main Circuit 13 ... 22 in·lb

Related Products