The T16-1.0 thermal overload relay is an economic electro-mechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10. Further features are the temperature compensation, trip contact (NC), signal contact (NO), automatic- or manual reset selectable, trip-free mechanism, STOP function and a trip indication. The overload relays are connected directly to the mini contactors or block contactors. Single mounting kits are available as accessory.
Specifications
Dimensions |
|
---|---|
Product Net Width | 45 mm |
Product Net Height | 76.7 mm |
Product Net Depth / Length | 53.5 mm |
Technical |
|
Setting Range | 0.74 ... 1.0 A |
Rated Operational Voltage | Auxiliary Circuit 600 V AC/DC Main Circuit 690 V AC |
Rated Operational Current (Ie) | 1 A |
Rated Operational Current AC-3 (Ie) | 1 A |
Rated Frequency (f) | Auxiliary Circuit 50 Hz Auxiliary Circuit 60 Hz Auxiliary Circuit DC Main Circuit 50 Hz Main Circuit 60 Hz |
Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV Main Circuit 6 kV |
Rated Insulation Voltage (Ui) | 690 V |
Number of Poles | 3 |
Number of Auxiliary Contacts NC | 1 |
Number of Auxiliary Contacts NO | 1 |
Number of Protected Poles | 3 |
Conventional Free-air Thermal Current (Ith) | Auxiliary Circuit NC 6 A Auxiliary Circuit NO 4 A |
Rated Operational Current AC-15 (Ie) | (120 V) NC 3 A (120 V) NO 0.5 A (240 V) NC 3 A (240 V) NO 0.5 A (400 V) NC 0.75 A (400 V) NO 0.5 A (500 V) NC 0.75 A (500 V) NO 0.5 A |
Rated Operational Current DC-13 (Ie) | (125 V) NC 0.55 A (125 V) NO 0.55 A (24 V) NC 1.25 A (24 V) NO 1.25 A (250 V) NC 0.27 A (250 V) NO 0.27 A (500 V) NC 0.15 A (500 V) NO 0.15 A (60 V) NC 0.55 A (60 V) NO 0.55 A |
Degree of Protection | IP20 |
Pollution Degree | 3 |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Flexible 1/2x 0.75 ... 1 mm² Flexible 1/2x 1 ... 2.5 mm² Rigid 1/2x 0.75 ... 4 mm² |
Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 4 mm² Flexible with Insulated Ferrule 1/2x 0.75 ... 4 mm² Flexible 1/2x 0.75 ... 4 mm² Solid 1/2x 0.75 ... 1.5 mm² Solid 1/2x 1.5 ... 4 mm² Stranded 1/2x 1 ... 4 mm² |
Tightening Torque | Auxiliary Circuit 1 ... 1.2 N·m Main Circuit 1.1 ... 1.5 N·m |
Wire Stripping Length | Auxiliary Circuit 9 mm Main Circuit 12 mm |
Recommended Screw Driver | Main Circuit Pozidriv 2 |
Power Loss | at Rated Operating Conditions per Pole 1.1 ... 2.0 W |
Suitable For | B6 BC6 B7 BC7 VB6 VBC6 VB7 VBC7 AS09 AS12 AS16 |
Standards | IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 |